4.0 Installation
4.1 General
After unpacking, check the PinTherm Connect and the external room sensor (if applicable) for
damage. Check that the type/model and the rated voltage are correct.
4.2 Installation PinTherm Connect
Determine a suitable place for installing the PinTherm Connect. Mount the PinTherm Connect
on a solid surface that can carry a minimum of 4 kg. We recommend mounting the PinTherm
Connect at a height of ±1.5m from the floor, at a well reachable place.
For cable gland use only cable glands fitted with strain relief, with a minimum fire class of UL94V2.
Check that the power supply has been switched off before connecting any wiring. If this is not the
case, the power supply must be switched off before you continue. When switching off the power
supply of the appliance to which connection is to be made, you should also refer to the technical
documentation/operating instructions for the appliance in question.
Connect the PinTherm Connect according to one of the supplied electrical diagrams which are in
the back of this technical book. To select the correct connection diagram, you need to know on
which type of device you will connect the PinTherm Connect. For a selection see also Annex I.
When applying a 0-10VDC signal, see the table below for the correct cable diameter and
associated length.
Diameter
Length
0.8mm
2
80 meter
1.0mm
2
100 meter
2
1.5mm
150 meter
4.3 Installation external room sensor
Place the external room sensor draft-free, in view of the appliance at a height of approx. 1.5m
from the floor. And connect the sensor to the appropriate terminals in the PinTherm Connect.
Refer to the chart below for the correct wire diameter and length.
Diameter
Length
2
0.8mm
80 meter
2
1.0mm
100 meter
2
1.5mm
150 meter
6
In this case, we advise the use of a shielded cable.
In this case, we advise the use of a shielded cable.