Clear Mode
In the clear mode (for selecting, refer to
"Changing the Modes of Operation"),
a.) a key or device, respectively,
b.) all devices (keys) of an ETS
channel, or
c.) the entire memory can be cleared.
Switching over to the clear mode:
1. Connect the battery to clip B (see
illustration on fold-out page). Display
J is activated.
2. Press channel selection keys G and
H simultaneously until both decimal
points are lit up (ca. 10 seconds.)
Display J shows '01.',
a.) Clearing a key or device, respectively
1. Actuate the key or device to be
cleared until the associated ETS
channel number blinks in the display.
(Actuation time: between 1 s and
10 s: e. g. 1 s for channel keys, 10 s
for All-ON or All-OFF key, respectively.)
2. By pressing the accept key for
approx. 3 s, the key or device can be
cleared from the memory. During the
clearing process, the display will be
reading '- -'. After the completion of
the clearing process, the channel
number will be displayed.
3. If the key or device is not to be cleared
the clearing process can be cancelled
by pressing any channel selection key.
24
b.) Clearing all keys or devices,
respectively, of an ETS channel
1. Select the ETS channel to be cleared
with the channel selection keys.
2. Pressing the accept key for approx.
3 s will initiate the clearing process
for the ETS channel selected. The
display will read 'CE' (CLEAR
ENTRY). After the completion of the
clearing process, the ETS channel
will reappear in the display.
c.) Clearing the entire memory
1. Pressing the accept key for approx.
3 s will initiate the clearing process
for the memory. The display will read
'AC' (ALL CLEAR).
2. After the completion of the clearing
process, the display will read '00'.
The device is again in the normal
service mode.
To return to the normal service mode
after the clearing processes remove the
battery.
Specifications
Power supply instabus EIB
Voltage
: 21 - 32 V DC
Power consumption
: max. 170 mW
External power supply (only for learning/
clearing mode)
Voltage
: 9 V battery,
type 6LR61
Power consumption
: max. 140 mW
Connection
instabus EIB
: Connecting
and branch
terminal
Battery
: Battery clip
for 9 V
battery block
Radio receive frequency : 433.42 MHz
Modulation
: ASK
(amplitude
shift keying)
Ambient temperature
: -5°C to + 45°C
Protective system
: IP 20
Subject to technical modifications.
Please hand this instructions manual
to your customer after installation.
Manufacturer's Warranty
Our products are under guarantee within
the scope of the statutory provisions.
Please return the unit postage paid to
our central service department giving
a brief description of the fault:
Berker GmbH & Co. KG
Klagebach 38
D-58579 Schalksmühle
Germany
Telephone: +49 (0) 23 55 / 90 5-0
Telefax:
+49 (0) 23 55 / 90 5-111
25

Advertenties

loading