17
Technical Information
Error Coding
Error Coding
There is an "ERROR BUFFER" inside the controller where it stores
some parameters when a FAIL occur.
These codes will remains stored even after a power off/on or a
stop/start command.
The serial win.710 (r/w) selects the fail event (0 to 3 for this
controller model), the serial command win.711(r/w) selects the
parameter you want to read (write here the number).
To read the value you have to send the command win.712 (r). Both
the win.710 and 711 are upper limited, so if you'll try to write a value
over the limit the controller will reply with "0x34" (out of range).
198/208
Special TV 301 Navigator Controller User Manual / 87-900-981-01 (E)