Systeeminstellingen - Danfoss AKC 72A Installatie- En Servicehandleiding

Regelaar voor koel- en vriessystemen
Inhoudsopgave

Advertenties

General factory settings
Thermostat
Defrost control
Difference ....................... 2
Demand defrost ........ OFF
SetpointLimit max ......... 50
Stop method ............ Temp
SetpointLimit min ........ -50
Max defrost time ........... 45
Thermostat mode ON/OFF
Stop temperature ............ 8
Night offset ...................... 0
Drain down ...................... 5
Monday day ............. 06:00
FanStart Temp/time . Temp
Monday night ........... 18:00
Max fan delay ............... 10
Alarm thermostat
Alarm destinations
Pulldown delay ........... 120
RFG not selected ............ 2
High Alarm delay .......... 30
RFG changed ................. 2
Low Alarm delay ........... 30
Overfloat evap. ............... 0
Air temp. Alarms ............. 1
Injection control
Def. per. exceeded ......... 2
Superheat max. K ......... 12
Fan del exceeded ........... 2
Superheat min. K ............ 3
AKS 32R error ................ 1
MOP control .............. OFF
S2 errror ......................... 1
MOP temperature ........... 0
Air on error ...................... 1
Air off error ...................... 1
S Def error ...................... 1
Door alarm ...................... 1
AKC 72A
Installatie en service
3. Systeeminstellingen wijzigen.
In dit hoofdstuk kunt u een aantal wijzigingen uitvoeren in de fabrieksinstellingen
waarmee de regelaar is opgestart (zie hoofdstuk 2).
Afhankelijk van uw keuze vindt u één van de onderstaande instellingen.
Configuration
Setting
Fan on period % ......... 100
Fan pulse period ........... 10
Fan stop on Sdef ...... OFF
Thermostat
Fan stop temp. ............ -10
Cutout temp. ......................... 3 ................................... 3 .................................. -21
DI alarm delay ................ 0
Air on % ................................ 0 ................................... 0 .................................. 100
Log interval ................... 15
Log temp. .. Thermostat air
Alarm thermostat
High alarm limit ..................... 10 ................................. 10 ................................ -15
Low alarm limit ...................... -3 .................................. -3 ................................. -30
Defrost control
Fan operation ....................... ON ............................... OFF ............................. OFF
Fan start temp. ..................... -3 .................................. -3 ................................. -10
Configuration
Fan when DI open ................ ON ............................... ON ............................... OFF
De fabrieksinstellingen kunnen niet geheel overeenkomen met uw wensen. Onder
de volgende punten kunnen alleen de belangrijkste instellingen worden
gewijzigd.
Als u andere instellingen wilt wijzigen dan de in dit hoofdstuk gegeven
voorbeelden verwijzen we u naar het menu-overzicht op pagina 39
RI.8A.B1.10 ©
Application-based factory selections
High temperature
High temperature
+ static defrost
+ elec. defrost
Danfoss 9/1998
Low temperature
+ elec. defrost
13