Super Digital Inverter
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the unit
should be lower than the height of the outdoor unit.
Standard installation
1,000 or
300 or
more
more
Installation of Outdoor Unit
•
Before installation, check the strength and horizontalness
of the base so that abnormal sounds do not emanate.
•
According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
150
Drain nipple
mounting hole
•
As shown in the figure below, install the foundation and
vibration-proof rubber pads to directly support the bottom
surface of the fixing leg that is in contact with and
underneath the bottom plate of the outdoor unit.
*
When installing the foundation for an outdoor unit with
downward piping, consider the piping work.
Fixing leg
Foundation
Foundation
Support the bottom surface of the
fixing leg that is in contact with and
underneath the bottom plate of the
EN
1,500 or
2,000 or
200 or
more
more
Drain hole
525
600
150
Drain hole
GOOD
Absorb vibration
with vibration-proof
rubber pads
GOOD
Bottom plate of
outdoor unit
outdoor unit.
If only the end of the
fixing leg is supported, it
may deform.
Foundation
Set the out margin of the anchor bolt to 15 mm or less.
more
•
When water is to be drained through the drain hose,
attach the following drain nipple and waterproof rubber
cap, and use the drain hose (Inner dia.: 16 mm) sold on
the market. Also seal the screws securely with silicone
material, etc., to prevent water from leaking.
Some conditions may cause dewing or dripping of water.
•
When collectively draining discharged water completely,
use a drain pan.
Drain nipple
For Reference
If a heating operation is to be continuously performed for a
long time under the condition that the outdoor temperature is
0 °C or lower, draining defrosted water may be difficult due to
the bottom plate freezing, resulting in trouble with the cabinet
or fan.
It is recommended to procure an anti-freeze heater locally in
order to safely install the air conditioner.
For details, contact the dealer.
9
NO GOOD
Do not support the
outdoor unit only with
the fixing leg.
15 or less
Waterproof rubber cap
(5pcs.)
Drain nipple
Waterproof rubber cap