eNet
eNet radiografische stuureenheid DALI 1-voudig mini
Switch-off delay
Dim up ramp
Dim down ramp
Dimming adjustment time
Run-on time
Manual saving of the scene
values
82580923
J0082580923
0 s ... 24 h
Basic setting: 0 s
0 s ... 24 h
Basic setting: 0 s
0 s ... 24 h
Basic setting: 0 s
1...60 s
Basic setting: 4 s
0 s ... 24 h
Basic setting: 0 s
On, Off
Basic setting: On
8/12
The load switches off after a
delay. Repeated switch-off
commands restart the delay
time. If the load has not yet
been switched off due to the
delay when a switch-on com-
mand comes, then the load
will remain on.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
Time between switch-on and
reaching switch-on brightness.
The light is switched on at
minimum brightness and then
dimmed to the switch-on
brightness.
Only applies to switch-on with
transmitters (short operation).
If scenes are recalled or swit-
ching uses logic modules, the
switch-on brightness is appro-
ached using so-called soft
dimming (not configurable).
Time until reaching minimum
brightness. The light is dim-
med to minimum brightness
and then switched off.
Only applies to switch-off with
transmitters (short operation).
If scenes are recalled or swit-
ching uses logic modules, the
system switches off directly.
Time from minimum
brightness until reaching maxi-
mum brightness (dimming
speed).
As soon as a run-on time has
been entered, the actuator will
no longer remain on perma-
nently, but only for the length
of the run-on time. The run-on
time is restarted if actuation is
repeated. This parameter is
directly connected to the
"Manual switch-off of run-on
time" parameter.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
Disables the saving of the cur-
rent brightness value as scene
value in an actuator for a com-
mand via a transmitter.
28.06.2016