Draadloze dimactor enkelvoudig DIN-rail
Run-on time
Behaviour after the end of the
disabling function
Behaviour on voltage return
Brightness on voltage return
Switch-off warning
32581602
10499444
0 s ... 24 h
Basic setting: 0 s
On
Off
no change
Last value
Basic setting: No change
On
Off
Last value
Configured brightness
Basic setting: Off
0...100 %
Basic setting: 100 %
On, Off
Basic setting: Off
12.03.2014
As soon as a run-on time has
been entered, the actuator will
no longer remain on perma-
nently, but only for the length
of the run-on time. The run-on
time is restarted if actuation is
repeated. This parameter is
directly connected to the
"Manual switch-off of run-on
time" parameter.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.
Behaviour of the output when
a block is removed.
Defines the behaviour of the
output after voltage return.
RMD design: Bus voltage
return
Brightness value, set by the
output after voltage return
(bus voltage). The parameter
"Behaviour after voltage
return" must be set to "Confi-
gured brightness".
Note: If the value is above the
set maximum brightness or
below the minimum
brightness, then the system
will switch to the appropriate
limit value.
If the switch-off warning is
active, then, during switch-off,
the systems dims to minimum
brightness within 30 seconds
and only then switches off. If
the parameter "Dim down
ramp" is configured as longer
than 30 s, then the length of
the dim down ramp is applied.
If, during the dim down opera-
tion, another command is
given, e.g. switch on or scene
recall, then the switch-off
warning stops and the com-
mand is executed. A switch-off
command restarts the time for
the switch-off warning.
Note: The set time apply to
operation using radio transmit-
ters. The device is switched
immediately when the Prog
button is pressed.