Danfoss VLT HVAC Basic Drive Snelgids pagina 33

Verberg thumbnails Zie ook voor VLT HVAC Basic Drive:
Inhoudsopgave

Advertenties

Snelgids
1
1
13-11 Comparator Operator
[0] Less Than
*[1] Approx. Equal
[2] GreaterThan
13-12 Comparator Value
-9999,0-9999,0, * 0,0
13-2* Timers
13-20 SL Controller Timer
0,00-3600,00, * 0,00
13-4* Logic Rules
13-40 Logic Rule Boolean 1
Zie par. 13-01, *[0] False
13-41 Logic Rule Operator 1
*[0] Disabled
[1] AND
[2] OR
[3] AND NOT
[4] OR NOT
[5] NOT AND
[6] NOT OR
[7] NOT AND NOT
[8] NOT OR NOT
13-42 Logic Rule Boolean 2
Zie par. 13-01, *[0] False
13-43 Logic Rule Operator 2
Zie par. 13-41, *[0] Disabled
13-44 Logic Rule Boolean 3
Zie par. 13-01, *[0] False
13-5* States
13-51 SL Controller Event
Zie par. 13-01, *[0] False
13-52 SL Controller Action
*[0] Disabled
[1] No action
[2] Select set-up 1
[3] Select set-up 2
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[25] Qstop
[26] DC Brake
[27] Coast
[28] Freeze output
[29] Start timer 0
[30] Start timer 1
Tabel 1.30
32
VLT HVAC Basic Drive Snelgids
[31] Start timer 2
[9] Automatic reset x 9
[32] Set digital out A low
[10] Automatic reset x 10
[33] Set digital out B low
[11] Automatic reset x 15
[34] Set digital out C low
[12] Automatic reset x 20
[35] Set digital out D low
[13] Infinite auto reset
[38] Set digital out A high
14-21 Automatic Restart Time
[39] Set digital out B high
0-600 s, * 10
[40] Set digital out C high
14-22 Operation Mode
[41] Set digital out D high
*[0] Normal operation
[60] Reset Counter A
[2] Initialisation
[61] Reset Counter B
14-27 Action At Inverter Fault
[70] Start timer 3
[0] Trip
[71] Start timer 4
*[1] Warning
[72] Start timer 5
14-28 Production Settings
[73] Start timer 6
*[0] No action
[74] Start timer 7
[1] Service reset
[100] Reset Alarm
[3] Software Reset
14-** Special Functions
14-29 Service Code
14-0* Inverter Switching
0-0x7FFFFFFF, * 0
14-01 Switching Frequency
14-3* Current Limit Ctrl.
[0] Ran3
14-4* Energy Optimising
[1] Ran5
14-40 VT Level
[2] 2.0 kHz
40-90%, * 90%
[3] 3.0 kHz
14-41 AEO Minimum Magneti-
[4] 4.0 kHz
sation
[5] 5.0 kHz
40-75%, * 66
[6] 6.0 kHz
14-5* Environment
[7] 8.0 kHz
14-50 RFI Filter
[8] 10.0 kHz
[0] Off
[9] 12.0kHz
*[1] On
[10] 16.0kHz
14-51 DC-link Voltage Compen-
14-03 Overmodulation
sation
[0] Off
[0] Off
*[1] On
*[1] On
14-08 Damping Gain Factor
14-52 Fan Control
0-100%, * 96
*[0] Auto
14-1* Mains on/off
[4] Auto Low temp env
14-12 Function at Mains
14-53 Fan Monitor
Imbalance
[0] Disabled
*[0] Trip
*[1] Warning
[1] Warning
[2] Trip
[2] Disabled
14-55 Output Filter
[3] Derate
*[0] No Filter
14-2* Reset Functions
[1] Sine-Wave Filter
14-20 Reset Mode
[3] Sine-Wave Filter with
*[0] Manual reset
Feedback
[1] Automatic reset x 1
14-63 Min Switch Frequency
[2] Automatic reset x 2
1-16 kHz, * 1
[3] Automatic reset x 3
15-** Drive Information
[4] Automatic reset x 4
15-0* Operating Data
[5] Automatic reset x 5
15-00 Operating Hours
[6] Automatic reset x 6
0-2147483647, * 0
[7] Automatic reset x 7
[8] Automatic reset x 8
MG18A310 – VLT® is een gedeponeerd handelsmerk van Danfoss
Parameterlijst
15-01 Running Hours
0-2147483647, * 0
15-02 kWh Counter
0-65535, * 0
15-03 Power Up's
0-2147483647, * 0
15-04 Over Temp's
0-65535, * 0
15-05 Over Volt's
0-65535, * 0
15-06 Reset kWh Counter
*[0] Do not reset
[1] Reset counter
15-07 Reset Running Hours Counter
*[0] Do not reset
[1] Reset counter
15-3* Alarm Log
15-30 Alarm Log:
Error Code 0-255, * 0
15-4* Drive Identification
15-40 FC Type
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-44 OrderedTypeCode
15-46 Frequentieomvormer
Ordering No
15-47 Power Card Ordering No
15-48 LCP Id No
15-49 Software ID Control Card
15-50 Software ID Power Card
15-51 Frequentieomvormer Serial
Number
15-53 Power Card Serial Number
16-** Data Readouts
16-0* General Status
16-00 Control Word
0-65535, * 0
16-01 Reference [Unit]
-4999,000-4999,000, * 0,000
16-02 Reference
% -200,0-200,0, * 0,0
16-03 Status Word
0-65535, * 0
16-05 Main Actual Value [%]
-200,00-200,00, * 0,00
16-09 Custom Readout
0,00-9999,00, * 0,00
16-1* Motor Status
16-10 Power [kW]
0,000-4,294, 967,500, *0,000
16-11 Power [hp]
0,000-2,294, 967,500 *0,000
16-3* Drive Status
16-30 DC Link Voltage
0-65535, * 0