1-63 Slip Compensation Time
Constant
0,05-5,00 s, * 0,10
1-64 Resonance Dampening
0-500%, * 100
1-65 Resonance Dampening Time
Constant
0,001-0,050 s, * 0,005
1-7* Start Adjustments
1-71 Start Delay
0,0-10,0 s, * 0,0
1-72 Start Function
[0] DC-houd/vertr. tijd
*[2] Coast/delay time
1-73 Flying Start
*[0] Disabled
[1] Enabled
1-8* Stop Adjustments
1-80 Function at Stop
*[0] Coast
[1] DC hold/MotorPreheat
1-82 Min Speed for Function at
Stop [Hz]
0,0-20,0 Hz, * 0,0
1-9* Motor Temperature
1-90 Motor Thermal Protection
*[0] No protection
[1] Thermistor warning
[2] Thermistor trip
[3] ETR warning 1
[4] ETR trip 1
1-93 Thermistor Source
*[0] None
[1] Analog input 53
[6] Digital input 29
2-** Brakes
2-0* DC-Brake
2-00 DC Hold/Motor Preheat
Current
0-160%, * 50
2-01 DC Brake Current
0-150%, * 50
2-02 DC Braking Time
0,0-60,0 s * 10,0
2-04 DC Brake Cut In Speed
0,0-400,0 Hz, * 0,0
2-1* Brake Energy Funct.
2-17 Over-voltage Control
[0] Disabled
*[2] Enabled
3-** Reference / Ramps
3-0* Reference Limits
3-02 Minimum Reference
(-4999,000) - 4999,000, * 0,000
3-03 Maximum Reference
(-4999,000) - 4999,000, * 50,000
Tabel 1.27
VLT HVAC Basic Drive Snelgids
Parameterlijst
3-1* References
3-10 Preset Reference
-100,00-100,00%, * 0,00
3-11 Jog Speed [Hz]
0,0-400,0 Hz, * 5,0
3-14 Preset Relative Reference
-100,00-100,00, * 0,00
3-15 Reference 1 Source
[0] No function
*[1] Analog in 53
[2] Analog in 54
[11] Local bus reference
3-16 Reference 2 Source
[0] No function
[1] Analog in 53
*[2] Analog in 54
[11] Local bus reference
3-17 Reference 3 Source
[0] No function
[1] Analog in 53
[2] Analog in 54
*[11] Local bus reference
3-4* Ramp 1
3-41 Ramp 1 Ramp up Time
0,05-3600,00 s, *Afhankelijk van
grootte
3-42 Ramp 1 Ramp Down Time
0,05-3600,00 s, *Afhankelijk van
grootte
3-5* Ramp 2
3-51 Ramp 2 Ramp up Time
0,05-3600,00 s, *Afhankelijk van
grootte
3-52 Ramp 2 Ramp down Time
0,05-3600,00 s, *Afhankelijk van
grootte
3-8* Other Ramps
3-80 Jog Ramp Time
0,05-3600,00 s, *Afhankelijk van
grootte
3-81 Quick Stop Ramp Time
0,05-3600,00 s, *Afhankelijk van
grootte
4-** Limits / Warnings
4-1* Motor Limits
4-10 Motor Speed Direction
[0] Clockwise
*[2] Both directions
4-12 Motor Speed Low Limit [Hz]
0,0-400 Hz * 0,0 Hz
4-14 Motor Speed High Limit
[Hz]
0,1-400 Hz, * 65,0 Hz
4-18 Current Limit
0-300%, * 110
MG18A310 – VLT® is een gedeponeerd handelsmerk van Danfoss
4-19 Max Output Frequency
0,0-400,0 Hz, * 65,0
4-4* Adj. Warnings 2
4-40 Warning Freq. Low
0,0-400,0 Hz, *400,0
4-41 Warning Freq. High
0,0-400,0 Hz, *400,0
4-5* Adj. Warnings
4-50 Warning Current Low
0,00-194,00 A, * 0,00
4-51 Warning Current High
0,00-194,00 A, * 194,00
4-54 Warning Reference Low
-4999,000-4999,000, *-4999,000
4-55 Warning Reference High
-4999,000-4999,000, *4999,000
4-56 Warning Feedback Low
-4999,000-4999,000, *-4999,000
4-57 Warning Feedback High
-4999,000-4999,000, *4999,000
4-58 Missing Motor Phase
Function
[0] Off
*[1] On
4-6* Speed Bypass
4-61 Bypass Speed From [Hz]
0,0-400,0, * 0,0
4-63 Bypass Speed To [Hz]
0,0-400,0, * 0,0
4-64 Semi-Auto Bypass Set-up
*[0] Off
[1] Enable
5-** Digital In/Out
5-0* Digital I/O mode
5-00 Digital Input Mode
*[0] PNP
[1] NPN
5-03 Digital Input 29 Mode
*[0] PNP
[1] NPN
5-1* Digital Inputs
5-10 Terminal 18 Digital Input
[0] No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
*[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire mode
[52] Run permissive
[53] Hand Start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
5-11 Terminal 19 Digital Input
Zie par. 5-10, *[0] No operation
5-12 Terminal 27 Digital Input
Zie par. 5-10, *[2] Coast inverse
5-13 Terminal 29 Digital Input
Zie par. 5-10, *[14 Jog]
5-3* Digital Outputs
5-34 On Delay, Digital Output
0,00-600,00 s, *0,01 s
5-35 Off Delay, Digital Output
0,00-600,00 s, *0,01 s
5-4* Relays
5-40 Function Relay
*[0] No operation
[1] Control ready
[2] Drive ready
[3] Drive ready/remote control
[4] Standby / no warning
[5] VLT running
[6] Running / no warning
[7] Run in range/no warning
[8] Run on ref/no warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
[82] SL digital output C
[83] SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode