PROBA 4

4.2 PROBA 4 Basisprint

Earth
8x Digital in contacts
strip-2
Dig.in-1
S1
(Fan failure gen.)
S2
Dig.in-2
(Cool failure gen.)
S3
Dig.in-3
(Heat failure gen.)
S4
Dig.in-4
(Door closed)
S5
Dig.in-5
(Ext. fatal alarm)
S6
Dig.in-6
(Ext. non-fatal al)
S7
Dig.in-7
*(Block)
S8
Dig.in-8
*(Airbag failure)
Com.
I C-bus for extension
2
+12V
SCL
For future use
SDA
GND
Shield only on one side to earth
A
B
GND
Shield only on one side to earth
RS485 Network in
Terminal jumpers J5 and J6 #
+12V
A
B
GND
Shield only on one side to earth
RS485 Network out
f.i. to Control Panel
#) ATTENTION
If PROBA 4 is first or last unit
in the RS485-LAN chain
place J5 and J6.
RS232 Factory use only
RXD-PC
No user connection
TXD-PC
GND
Ethernet connection
VDH
317.100009
EMC Ferriet on the ETHERNET-cable,
as close
as possible
to the PCB.
USB-1 (type-A)
connection
VDH
317.100009
EMC Ferriet on the USB-cable,
as close
as possible
to the PCB.
SD-Card
USB
type-B
Ethernet
USB
connector
connector
to Earth
(type-A)
strip-2
Value's between brackets ()
are default settings.
Tekening 100334
Fig. 7
Page 1: Drawing 100334w2
Page 2: Drawing 100790w0
Page 1 of 2
WARNING
HIGH
VOLTAGE
0V
Connector to
Analog I/O PCB
Earth strip-1 on mounting plate
Mat.:
PCB's on mountingplate
All shields of the
Opm.:
shieled cable's must be
connected to the earth-
strip first.
Sa100334w2.cdr
File:
Doc.nr: 151061
from Mains
Power
Supply
PE
Wnr.
Datum Gew.
Door
Omschr.:
W1
08-07-2010
B
Getek.:
W2
20-09-2010
B
Datum:
Tek.nr.:
Pagina 14
Versie: 1.1
PCB Supply
PCB PE
PE (green/yellow)
connected to
Earth strip-1
N (blue)
PCB Supply
85-264Vac
L1 (black)
50-60Hz
16x Relay outputs
C-1
1: Relay SPST NC/C
(Fatal Alarm)
NC-1
C-2
2: Relay SPST NC/C
NC-2
(Non Fatal Alarm)
C-3
NC-3
3: Relay SPDT NO/NC/C
(Door Lock)
NO-3
C-4
NC-4
4: Relay SPDT NO/NC/C
(Fan Reverse)
NO-4
5: Relay SPST NO (Cooling-1)
6: Relay SPST NO (Cooling-2)
7: Relay SPST NO (Cooling-3)
8: Relay SPST NO (Heating-1)
9: Relay SPST NO (Heating-2)
10: Relay SPST NO (Heating-3)
COM: Relays Common 5..16
11: Relay SPST NO (Fan-1)
12: Relay SPST NO (Fan-2)
ATTENTION:
Relays 5:.....16:
have one common
connection
13: Relay SPST NO (Fan-3)
14: Relay SPST NO (Gassing)
15: Relay SPST NO (Ventilation)
16: Relay SPST NO (Humidify)
ATTENTION:
Separate
all I/O-cable's (leftside)
from
power and control (relay)
cable's (rightside)
Housing
PCB
PE
PE
Connections PROBA 4 Main PCB
(for Analog I/O PCB see page-2)
B
Schaal:
1:1
07-04-2010
A4-10
Kast:
Par.:
Projection:
100334
RODEN
HOLLAND