Download Inhoudsopgave Inhoud Print deze pagina

Danfoss VLT HVAC Basic Drive FC 101 Bedieningshandleiding pagina 47

Verberg thumbnails Zie ook voor VLT HVAC Basic Drive FC 101:
Inhoudsopgave

Advertenties

VLT® HVAC Basic Drive FC 101
Bedieningshandleiding
Parameter
Bereik
V/50 Hz/IT-grid[31] 525–600
V/50 Hz/Delta[32] 525–600 V/50
Hz[100] 200–240 V/60 Hz/IT-
grid[101] 200–240 V/60 Hz/
Delta[102] 200–240 V/60
Hz[110] 380–440 V/60 Hz/IT-
grid[111] 380–440 V/60 Hz/
Delta[112] 380–440 V/60
Hz[120] 440–480 V/60 Hz/IT-
grid[121] 440–480 V/60 Hz/
Delta[122] 440–480 V/60
Hz[130] 525–600 V/60 Hz/IT-
grid[131] 525–600 V/60 Hz/
Delta[132] 525–600 V/60 Hz
Parameter 1-00
[0] Open loop (Zonder terug-
Configuration
koppeling)[3] Closed Loop (Met
Mode (Configu-
terugkoppeling)
ratiemodus)
Parameter 1-10
*[0] Asynchron (Asynchroon)
Motor Con-
[1] PM, non-salient SPM (PM,
struction (Mo-
niet-uitspringende SPM)[3] PM,
torconstructie)
salient IPM (PM, uitspringende
IPM)
Danfoss A/S © 2019.11
Standaard
Gebruik
[0] Open loop
Selecteer [3] Closed loop (Met terugkoppeling).
(Zonder ter-
ugkoppeling)
[0] Asynchron
Door het instellen van deze parameter kan de instelling van
(Asynchroon)
de volgende parameters wijzigen:
Parameter 1-01 Motor Control Principle (Motorbesturing-
sprincipe).
Parameter 1-03 Torque Characteristics (Koppelkarakteris-
tiek).
Parameter 1-08 Motor Control Bandwidth (Bandbreedte
motorbesturing).
Parameter 1-14 Damping Gain (Verst. demping).
Parameter 1-15 Low Speed Filter Time Const (Filtertijdcon-
stante lage snelh.).
Parameter 1-16 High Speed Filter Time Const (Filtertijdcon-
stante hoge snelh.).
Parameter 1-17 Voltage Filter Time Const (Filtertijdcon-
stante spanning).
Parameter 1-20 Motor Power (Motorvermogen).
Parameter 1-22 Motor Voltage (Motorspanning).
Parameter 1-23 Motor Frequency (Motorfrequentie).
Parameter 1-24 Motor Current (Motorstroom).
Parameter 1-25 Motor Nominal Speed (Nom. motorsnel-
heid).
Parameter 1-26 Motor Cont. Rated Torque (Cont. nom. mo-
torkoppel).
Parameter 1-30 Stator Resistance (Rs) (Statorweerstand
(Rs)).
Parameter 1-33 Stator Leakage Reactance (X1) (Statorlek-
reactantie (X1)).
Parameter 1-35 Main Reactance (Xh) (Hoofdreactantie
(Xh)).
Parameter 1-37 d-axis Inductance (Ld) (Inductantie d-as
(Ld)).
Parameter 1-38 q-axis Inductance (Lq) (Inductantie q-as
(Lq)).
Programmeren