16.4 Modbus slave-communicatieparameters

MODBUS
Speed / Vitesse :
Bit number / Nbre de bits :*
Stop bit / Bit de stop :
Parity / Parité :
Mode :
ModBus Points
MODBUS adress**
PD_Cmd_P1
PD_Cmd_P2
PD_Cmd_P3
PD_Cmd_P4
PriP1_Alarm_On
PriP2_Alarm_On
SecP3_Alarm_On
SecP4_Alarm_On
PD_High_Alarm
PD_Main_Alarm
Fooling_Alarm
ThermTr_Alarm
PD_Triac_Output
SAFETY_FCT
AFF_Leg_active
Remote_Control_Rev
PC_Distrib_Com
AFF_FD20
AFF_FD22
BOOSTER
ECO
PD_Pumps_Fault
Tank_load
SW AL Version
PA10_Speed_P1P2
PA10_Speed_P3P4
PA10_valve1
PA10_valve2
SP_Apilot
S1_10
S2_10
S3_10
S4_10
S5_10
S6_10
pt1_10
pt2_10
DT_recup_min10
S1_PID_SP_10
SP_T_Amb_S5_10
Solar_Option_Ana
High_Alm_Reset
Pump fault Reset
DeltaT_ByPass
SP_T_Sec_Outlet
PC_Distrib_distant
ThTr_setpoint
* For some supervisors, it is necessary to implement BOOL as int16
** For some supervisors, remove 1 to adress number (ex : S1_10 adress=49)
9600
8
1
None / Aucune
RTU
Type
Sub-type
Read Only digital
15
HR _16
BOOL
16
HR _16
BOOL
17
HR _16
BOOL
18
HR _16
BOOL
19
HR _16
BOOL
20
HR _16
BOOL
23
HR _16
BOOL
24
HR _16
BOOL
27
HR_16
BOOL
28
HR_16
BOOL
30
HR_16
BOOL
32
HR_16
BOOL
33
HR _16
BOOL
35
HR_16
BOOL
36
HR_16
BOOL
37
HR_16
BOOL
38
HR_16
BOOL
39
HR_16
BOOL
40
HR_16
BOOL
41
HR_16
BOOL
42
HR_16
BOOL
43
HR_16
BOOL
44
HR_16
BOOL
(16 bit integer/Entier 16 bit)*
Read Only Analogic
34
HR_16
int16
45
HR_16
int16
46
HR_16
int16
47
HR_16
int16
48
HR_16
int16
49
HR_16
int16
50
HR_16
int16
51
HR_16
int16
52
HR_16
int16
53
HR_16
int16
54
HR_16
int16
55
HR_16
int16
56
HR_16
int16
57
HR_16
int16
61
HR_16
int16
62
HR_16
int16
63
HR_16
int16
64
HR_16
int16
(16 bit integer/Entier 16 bit)*
Read-Write digital
201
HR_16
BOOL
202
HR_16
BOOL
(16 bit integer/Entier 16 bit)*
Read-Write Analogic
210
HR_16
int16
211
HR_16
int16
212
HR_16
int16
213
HR_16
int16
(16 bit integer/Entier 16 bit)*
In case of multiple controllers, change ModBus controler slave number
Parameter="DEVICE ID"
Mode
Value
R
0=Off, 1=On
Command(e) P1
R
0=Off, 1=On
Command(e) P2
R
0=Off, 1=On
Command(e) P3
R
0=Off, 1=On
Command(e) P4
R
0=OK, 1=Alarm
P1 Fault P1
R
0=OK, 1=Alarm
P2 Fault P2
R
0=OK, 1=Alarm
P3 Fault P3
R
0=OK, 1=Alarm
P4 Fault P4
R
0=OK, 1=Alarm
S1 High Temp Alarm
R
0=OK, 1=Alarm
General default
R
0=OK, 1=Alarm
Fooling alarm (S3)
R
0=OK, 1=Alarm
Therm.Treat. Failed
R
0=Off, 1=On
230V Triac output
R
0=Off, 1=On
Safety function
R
0=Off, 1=On
Therm.Treat. On going
R
0=Off, 1=On
Remote control
R
0=Internal, 1=External
AlfaPilot external setpoint
R
0=Off, 1=On
Heating mode
R
0=Off, 1=On
Cooling mode
R
0=Off, 1=On
BOOSTER activated
R
0=Off, 1=On
ECO activated
R
0=Off, 1=On
Synthesis pump(s) fault
R
0=Off, 1=On
Tank loaded
R
Software version
R
%
Primary pump signal
R
%
Secondary pump signal
R
%
Control vlave 1 signal
R
%
Control vlave 2 signal
R
°C
AlfaPilot Setpoint
R
°C
Sensor 1 measurement
R
°C
Sensor 2 measurement
R
°C
Sensor 3 measurement
R
°C
Sensor 4 measurement
R
°C
Sensor 5 measurement
R
°C
Sensor 6 measurement
R
°C
Sensor Pt1 measurement
R
°C
Sensor Pt2 measurement
R
°C
Min DT energy recov
R
°C
Calculated S1 setpoint
R
°C
Ambiant temp. Setpoint
0=no/pas/keine Option
1=Solar Flow
R
2=Alfa_store A
0 for AquaFirst, AquaEfficiency
3=AlfaPilot
4=Aqua_Heating
R/W
1=Reset fault. Pulse point necessary 30 seconds On/Off
R/W
R/W
°C
Delta T bypass (S4-S3)
R/W
°C
S1 fixed setpoint (DHW)
R/W
°C
AlfaPilot external setpoint on Pt2
R/W
°C
Thermal treatment setpoint
56
Comment