■ ■ ■ ■ ■ Algemene technische gegevens
Netvoeding (L1, L2, L3):
Netvoeding 200 - 240 V units .......................................................................... 3 x 200/208/220/230/240 V ±10%
Netvoeding 380 - 460 V units .......................................................................... 3 x 380/400/415/440/460 V ±10%
Netvoeding 550-600 V units ...................................................................................... 3x 550/575/600 V ±10%
Ingangsfrequentie ........................................................................................................................ 50/60 Hz +/- 1%
Max. onbalans van de netvoeding: ................................................................................................................. ±3%
VLT 6002-6011 / 380-460 V en 550-600 V en VLT 6002-6005 / 200-240 V .. ±2,0% van nominale netvoeding
VLT 6016-6072 / 380-460 V en 550-600 V en VLT 6006-6032 / 200-240 V .... ±1,5% van nominale netvoeding
VLT 6075 - 6550 / 380 - 460 V en VLT 6042 - 6062 / 200 - 240 V .................. ±3,0% van nominale netvoeding
VLT 6100-6275/550-600 V .................................................................................... 13% van nominale netvoeding
(λ) .................................................................................................. 0,90/1,0 bij nominale belasting
Ware arbeidsfactor
Verschuivingsarbeidsfactor (cos. ϕ) ................................................................................ dicht bij eenheid (>0,98)
Aantal schakelingen op ingang L1, L2, L3 ................................................................. ongeveer 1 keer/ 2minuten
Max. nominale waarde kortsluiting ........................................................................................................ 100.000 A
VLT-uitgangsgegevens (U, V, W):
Uitgangsspanning ........................................................................................................... 0 - 100% van netvoeding
Uitgangsfrequentie ........................................................................................................... 0 - 120 Hz, 0 - 1000 Hz
Nominale motorspanning, 200 - 240 V units ................................................................... 200/208/220/230/240 V
Nominale motorspanning, 380 - 460 V units ............................................................ 380/400/415/440/460/500 V
Nominale motorspanning, 550 - 600 V units ......................................................................................... 550/575 V
Nominale motorfrequentie ........................................................................................................................ 50/60 Hz
Schakelen aan uitgang ..................................................................................................................... Onbegrensd
Aan-/uitlooptijden ............................................................................................................................... 1- 3600 sec.
Koppelkarakteristieken:
Startkoppel ................................................................................................................ 110% gedurende 1 minuut.
Startkoppel (parameter 110 Hoog startkoppel) ...................................... Max. koppel: 160% gedurende 0,5 sec.
Versnellingskoppel ......................................................................................................................................... 100%
Overbelastingskoppel .................................................................................................................................... 110%
Stuurkaart, digitale ingangen:
Aantal programmeerbare digitale ingangen ......................................................................................................... 8
Klemnrs. ................................................................................................................. 16, 17, 18, 19, 27, 29, 32, 33
Spanningsniveau ............................................................................................................. 0 - 24 V DC (PNP logica)
Spanningsniveau, logische ´0´ ................................................................................................................. < 5 V DC
Spanningsniveau, logische ´1´ ............................................................................................................... > 10 V DC
Maximumspanning op ingang ................................................................................................................... 28 V DC
Ingangsweerstand, R
................................................................................................................................... 2 kΩ
i
Scantijd per ingang ................................................................................................................................... 3 msec.
Betrouwbare galvanische isolatie: alle digitale ingangen zijn galvanisch geïsoleerd van de netvoeding (PELV).
Daarnaast kunnen de digitale ingangen van de andere klemmen op de stuurkaart worden geïsoleerd door een
externe 24 V DC-voeding aan te sluiten en schakelaar 4 te openen. Zie Schakellaars 1-4.
Stuurkaart, analoge ingangen:
Aantal programmeerbare analoge spanningsingangen/thermistoringangen ...................................................... 2
Klemnrs. ....................................................................................................................................................... 53, 54
Spanningsniveau ............................................................................................................. 0 - 10 V DC (schaalbaar)
Ingangsweerstand, R
.................................................................................................................. ongeveer 10 kΩ
i
Aantal programmeerbare analoge stroomingangen ............................................................................................ 1
Klemnr. aarde .................................................................................................................................................... 55
Stroombereik .................................................................................................................. 0/4 - 20 mA (schaalbaar)
................................................................................................................................... 200 Ω
Ingangsweerstand, R
i
Resolutie .......................................................................................................................................... 10 bit + teken
Nauwkeurigheid op ingang .............................................................................. Max. fout 1% van volledige schaal