Alarm Code
A.E81
A.EB0
A.EB2
A.EB3
A.EC0
A.EC1
A.E1F
YASKAWA EUROPE TOMP YEUOS7S 01A – Sigma-7 Series Advanced Safety Module – Instruction Manual
Cause
A safety module different
from the one used before
has been connected.
An error occurred in the
system of the safety
module.
The settings of the safety
functions do not conform
to the settings of the test
without motor function.
An error occurred in
the HWBB circuit of the
SERVOPACK.
A different safety module
was connected to the
SERVOPACK.
The safety module has been
installed correctly and is
waiting for parameterisation.
Mismatch of software
version between
SERVOPACK and safety
module.
Actions
• Check the model of the connected safety
module.
• Execute Fn014 (Resetting Configuration
Errors in Option Modules), and turn the
power OFF and ON again.
• Restart the system.
• Check the connection between the
SERVOPACK and the safety module.
• Make improvements in the EMC
installation environment.
• Replace the safety module.
• Replace the SERVOPACK.
Check the set value of Pn00C. The value of
Pn00C.0 (Selection of Test without a Motor)
needs to be set to 0.
• Restart the system.
• Check the connection between the
SERVOPACK and the safety module.
• Replace the SERVOPACK.
• Replace the safety module.
Download the product manual and follow
the instructions described in connection with
setting up the safety module.
• Check the software version of the
SERVOPACK.
• Check the software version of the safety
module.