MAIN SAFETY DEVICES
12 MAIN SAFETY DEVICES
Com pre ssor Prot e c t ion
High pressure switch:
This switch cuts out the operation of the compressor when the discharge pressure exceeds the setting.
Fa n M ot or Prot e c t ion
When the fan motor current is reached to the setting, motor output is decreased.
The other way, when the fan motor current becomes lower, limitation is cancelled.
Model
For Compressor
Pressure Switches
High
Low
for control
Fuse
1~ 230V 50Hz
CCP Timer
Setting Time
For Condenser Fan Motor
Internal Thermostat
For Control Circuit
Fuse on PCB
15
PMML0398B rev.3 - 01/2020 - P5416651
-
Cut-Out
MPa
Cut-In
MPa
Cut-Out
MPa
Cut-In
MPa
-
A
-
min.
-
A
RAS-2HVNP1
RAS-2.5HVNP1
RAS-3HVNC1
Automatic Reset, Non-Adjustable (each one for each compressor)
4.15
3.20
0.20
0.30
40
Non-Adjustable
Automatic Reset, Non-Adjustable (each one for each motor)
3
5