3.5 Weekly Timer
Under Weekly Timer , six independent changeover times can be entered (password protected).
Confi guration I Timer I WeeklyTimer 1-6 I
Confi guration I Timer I WeeklyTimer 1-6 I
Under «Weekly Timer», six independent changeover times can be entered. The time, fan speed and relevant setpoint
value can be set. These times override what is entered in the daily timer. The table on the next page shows the operat-
ing functions that must be entered.When you define a setting, you must ensure that a changeover time is activated.
Weekly Timer-settings with a higher period number preseds those with a lower number.
Active
Timer – time ON (period 1-4)
Timer – time ON (period 1-4)
Timer – speed (period 1-4)
Timer – temperature (period 1-4)
Timer – temperature ON/OFF (period 1-4)
Timer – time OFF (period 1-4)
Timer – day OFF (period 1-4)
Timer - active YES/NO
Please note that you can set different setpoint values for the temperature in the different changeover periods. These
will override the setpoint value under: Temperature I Setting. If you want to set the temperature manually the setting
Temperature ON/OFF must be in the OFF-position.
*
Under Menu I Speed adjustment I you can adjust the fans to the preferred air quantity.
(You can also select Manual here. Under Menu I Fans I Fan control I Manual, you can set the fan speeds.
The unit will operate on this setting in the period in question.)
** Please note that you can set different setpoint values for the temperature in the different changeover periods.
These values will override the temperature setpoint value set under Menu I Temperature I Setting.
3.6 Temperature Setting, Main Sensor
Here you set the temperature (setpoint value) that you want the unit to maintain (main sensor). If you want other
values during the 24-hour period, these can be set under Timer .
Menu:
Temperature I Setting
Temperature I Setting
Parameter name
Setting range
Setting
10 - 30
3.7 Speed Stage 1, Supply Air
Sets the desired speed for stage 1.
This applies only to units that have infinitely variable fan control.
Menu:
Fan control I Speed setting I Supply air I Speed 1
Fan control I Speed setting I Supply air I Speed 1
Parameter name
Setting range
Speed 1
0 - 100
All manuals and user guides at all-guides.com
Setting line
Setting line
OFF/ON
ON
Mon
Mon-Sun
06.00
00.00-23.59
0-3 *
1
10-40 **
20
°C
ON/OFF
°C
OFF
20.00
00.00-23.59
Fri
Mon-Sun
Unit
Default value
°C
20
Unit
Default value
%
35
51