Download Inhoudsopgave Inhoud Print deze pagina

Kemper KHS Hygiene Flush Box PRO Inbouw- En Bedieningshandleiding pagina 93

Verberg thumbnails Zie ook voor KHS Hygiene Flush Box PRO:
Inhoudsopgave

Advertenties

7.2
Troubleshooting chart
Aerator set/ (FL/CV)
Aerator set/ (FL/CV)
Aerator set/ (FL/CV)
Float switch
Trap
Magnetic safety catch
Info!
PRO status lights
Status
green
In function
flashing green
Wi-Fi active
yellow
CAN bus active
flashing yellow
CAN bus + Wi-Fi active
magenta
Update
white
Reset
V1 / V2
green
Standby
blue
Flushing active
red
Error
orange
Warning
red & blue
Flushing active and current error
No clean spray cone from aerator
set.
No water from aerator.
Aerator dripping.
Float switch triggers fault signal. Backflow in connected drainpipe//
Odour!
Reversible cover doesn't close
flush with wall.
Calcification of FL or
aerator.
Non-compliance with the recom-
mended replacement interval.
Clogging!
FL installed wrong way round.
Solenoid valve doesn't close
properly.
trap due to
clogging.
No water in trap.
Anti-siphon trap not
fitted correctly.
Magnetic safety catch not
installed correctly/ only one of
the catches moved.
Plaster residue in the frame.
Guide bolts under the reversible
cover not inserted in the holes
provided in the FM frame.
Info!
PURE status lights
V1 / V2
green
yellow
blue
red
red & blue
Interval time (h) + flush duration (min)
green
flushing green
© www.kemper-group.com – 07.2024 / K410068903016-00 93 /108
Clean FL/aerator,
replace if necessary.
Install FL the right way round. The
aerator's outer gasket must point in the
direction of flow (upwards).
Remove solenoid valve and clean,
replace if necessary.
Check whether the drainpipe was de-
signed according to DIN 1986-100 in
conjunction with
EN 752 and EN 12056.
Float switch
Check manually.
Check cable connection from the float
switch to the
controller.
Perform manual flushing.
Fit anti-siphon trap correctly.
Install magnetic safety catch
correctly/move both
catches into the same position.
Remove plaster residue from
the frame.
Insert guide bolts under the reversible
cover into the holes provided in the FM
frame.
In function
Water exchange group selection
Flushing active
Error
Flushing active and current error
Selection
Selection confirmed

Advertenties

Inhoudsopgave
loading

Deze handleiding is ook geschikt voor:

Khs hygiene flush box pureKhs hygiene flush box lite

Inhoudsopgave