Troubleshooting Chart - Kemper KHS Hygiene Flush Box PRO Inbouw- En Bedieningshandleiding

Verberg thumbnails Zie ook voor KHS Hygiene Flush Box PRO:
Inhoudsopgave

Advertenties

EN
7.2
Status
Component
LED
red
PURE control unit
red
PURE control unit
red
PURE control unit
red
PURE control unit
red
PURE control unit
red
PURE control unit
red
PURE control unit
PURE control unit
Flow and temperature
sensor (Pt1000)
Flow and temperature
sensor (Pt1000)
Solenoid valve
Solenoid valve
92 /108 – K410068903016-00 / 07.2024 – © www.kemper-group.com

Troubleshooting chart

Malfunction
Interval LED 2 h lights up green.
Interval LED 6 h lights up green.
Interval LED 12 h lights up green. Update file on the USB stick could
Interval LED 24 h lights up green. Update error!
Interval LED 48 h lights up green. Update could not be decrypted.
Interval LED 72 h lights up green. There was no update with the
Interval LED 168 h lights up
green.
Press button malfunction.
Incorrect values displayed.
No signal!
Solenoid valve does not close/
open properly.
Water flow at the aerator is low.
Possible cause of fault
No valve recognised.
Waterlogging detected.
Hose connectors still mounted?
not be read.
correct name on the drive.
The software update version is
older than the existing one.
Dirt behind press button.
Clogging!
Check whether there is at least 1
bar pressure.
Cable not connected correctly
/faulty.
Plug contact/solenoid valve faulty
or clogging before the fine strainer.
Contamination before the fine
strainer on the solenoid valve.
Recommendation
Check cable and connections in the
controller,
replace if necessary.
Check whether the drainpipe was de-
signed according to DIN 1986-100 in
conjunction with EN 752 and EN 12056.
Check the float switch function manually.
Check the cable connection of the float
switch on the controller.
Install aerator set.
Check whether the correct file name is
present on the USB stick.
Check that only the latest update file is
present on the USB stick.
Check that only the latest update file is
present on the USB stick.
Download the latest update file from the
homepage.
No update required, or use the latest
version from the Kemper Homepage.
Remove press button and clean with
compressed air.
Remove flow and temperature sensor
and clean,
replace if necessary.
Remove solenoid valve and FL insert.
Clean manually if the flow rate deviates.
Check cable and connections in the
controller,
replace if necessary.
Remove solenoid valve and clean, check
plug contact, replace if necessary.
Remove solenoid valve and clean, repla-
ce if necessary, or check FL/aerator.