Download Print deze pagina

Panasonic WH-SDC12H6E5 Installatiehandleiding pagina 27

Lucht-naar-water warmtepomp binnenunit
Verberg thumbnails Zie ook voor WH-SDC12H6E5:

Advertenties

13. External Error Signal
Set when external error display unit is installed.
Turn on Dry Contact SW when error happened.
(CAUTION) Does not display when there is no Optional PCB.
When error occurs, error signal will be ON.
After turn off "close" from the display, error signal will still remain ON.
14. Demand control
Set when there is demand control.
Adjust terminal voltage within 1 ~ 10 V to change the operating current limit.
(CAUTION) Does not display when there is no Optional PCB.
Analog input
Rate
[v]
[%]
0.0
not activate
0.1 ~ 0.6
0.7
not
10
activate
0.8
0.9 ~ 1.1
10
1.2
15
10
1.3
1.4 ~ 1.6
15
1.7
20
15
1.8
1.9 ~ 2.1
20
2.2
25
20
2.3
2.4 ~ 2.6
25
2.7
30
25
2.8
2.9 ~ 3.1
30
3.2
35
30
3.3
3.4 ~ 3.6
35
3.7
40
35
3.8
15. SG ready
Initial setting: No
Switch operation of heat pump by open-short of 2 terminals.
Setting belows are possible
SG signal
Working pattern
Vcc-bit1
Vcc-bit2
Open
Open
Normal
Short
Open
Heat pump and Heater OFF
Open
Short
Capacity 1
Short
Short
Capacity 2
Capacity setting 1
- Heating capacity ___%
- DHW capacity ___%
Capacity setting 2
- Heating capacity ___%
- DHW capacity ___%
16. External Compressor SW
Set when external compressor SW is connected.
SW is connected to external devices to control power consumption, ON signal will
stop compressor's operation. (Heating operation etc. are not cancelled).
(CAUTION) Does not display if there is no Optional PCB.
If follow Swiss standard power connection, need to turn on DIP SW of main unit
PCB. ON/OFF signal used to ON/OFF tank heater (for sterilization purpose)
Initial setting: No
Initial setting: No
Analog input
Rate
[v]
[%]
3.9 ~ 4.1
40
4.2
45
4.3
4.4 ~ 4.6
45
4.7
50
4.8
4.9 ~ 5.1
50
5.2
55
5.3
5.4 ~ 5.6
55
5.7
60
5.8
5.9 ~ 6.1
60
6.2
65
6.3
6.4 ~ 6.6
65
6.7
70
6.8
6.9 ~ 7.1
70
7.2
75
7.3
Set by SG ready setting of remote controller
Initial setting: No
System setup
Bivalent connection
External SW
Solar connection
External error signal
Select
System setup
External SW
Solar connection
External error signal
Demand control
Select
Analog input
[v]
7.4 ~ 7.6
7.7
40
80
7.8
7.9 ~ 8.1
8.2
45
85
8.3
8.4 ~ 8.6
8.7
50
90
8.8
8.9 ~ 9.1
9.2
55
95
9.3
9.4 ~ 9.6
9.7
60
100
9.8
9.9 ~
65
*A minimum operating current is applied on each model for
protection purpose.
*0.2 voltage hysteresis is provided.
* The value of voltage after 2nd decimal point are cut off.
70
System setup
Solar connection
External error signal
Demand control
SG ready
Select
System setup
External error signal
Demand control
SG ready
External compressor SW
Select
Confi rm
Confi rm
Rate
[%]
75
75
80
80
85
85
90
90
95
95
100
Confi rm
Confi rm
17:26, Wed
17:26, Wed
17:26, Wed
17:26, Wed
27

Advertenties

loading

Deze handleiding is ook geschikt voor:

Wh-sdc16h6e5