Installation
First remove the wallplate from the back of the unit
J
From the top left hand corner of the wallplate, there
J
must be clearances of at least 140mm to the right,
15mm to the left, 30mm above and 100mm below in
order to mount the plug-in module.
Before mounting the unit ensure the 4 DIL switches
J
on the rear of the unit have been moved to the
required settings (see below). Factory preset is 7-day,
with Optimum Start and Chrono-proportional control OFF.

DIL Switch Settings

All models
1
Sw
5/2 day programming
2
Sw
Optimum start contoller enabled
3
Sw
Chrono-proportional control
TP7000, M & RF models with 3/6 cycles per hour option
4
Sw
Chrono-proportional, 6 cycles / hour
NOTE
Use Chrono 3 for high thermal inertia systems, e.g. fl oor standing cast iron boilers
Use Chrono 6 for low thermal inertia systems, e.g. low water content boilers and
combi boilers
4
7 day programming
Optimum start contoller disabled
On/Off control
Chrono-proportional, 3 cycles / hour