Option 90 - De ne remote sensor type, "A" models only
This allows type of remote sensor input type to be
de ned. Press + until Option 90 is displayed, use V
and Λ to select required setting.
Setting 0 No remote sensor tted
Setting 1 Remote room or duct sensor tted, internal sensor disabled,
Setting 2 Remote limit sensor tted, refer to option 93 to de ne set-point
Setting 3 Con gured as digital input for window, card reader or
Option 93 - Set limit sensor set-point, "A" models only,
(option 90 set to 2)
This allows the thermostat limit sensor to be set,
typical application is oor heating. Press + until
Option 93 is displayed, use V and Λ to select
required setting. If the temperature sensed by the
limit sensor exceeds the limit setting the output will
be turned o until the temperature has dropped by
2°C. "F10" will ash in the display while the output
is disabled.
Setting
Option 94 - Con gure digital input switch type, "A" models only,
(option 90 set to 3)
This allows switch type of digital input to be
con gured. Press + until Option 94 is displayed, use
V and Λ to select required setting.
Setting 0 Contacts NC, open circuit contact to force unit into
Setting 1 Contacts NO, short circuit contacts to force unit into
10
(Factory setting)
teleswitch, refer to option 94 to de ne o/c or s/c.
Any value between 20 - 50°C (Factory setting is 27°C)
thermostat mode, short circuit contacts to return to
normal operation
thermostat mode, open circuit contacts to return to normal
operation (Factory setting)