Mounting procedure
Package contents for surface-mounted installation (Fig. 3.1)
Package contents for concealed installation (Fig. 3.2)
Product components (Fig. 3.3)
A Connection module power supply lead, surface-mounted
B Connection module power supply lead, concealed
C Sensor module
D Shroud
E Designer trim, round or square
Product dimensions
Surface-mounted / concealed (Fig. 3.4) IS 3360, IS 3360 MX, IS 345
Surface-mounted / concealed (Fig. 3.5) IS 345 MX
Surface-mounted / wall-mounted (Fig. 3.6) IS 3180

4. Electrical installation

The mounting location should be at least 50 cm away from other lights because heat
radiated from these may activate the system. An optional corner wall mount (product
no. 648015 black or 035174 white) is available for mounting the IS 3180.
For wiring up the motion detectors, the following applies: under section 6 of VDE
0100 520, a multiple-core lead containing both the mains voltage leads and the
control leads (e.g. NYM 5 × 1.5) may be used for the wiring between sensor and DALI
Application Controller. The lead between DALI Application Controller and sensor must
be no longer than 300 m (for 1.5 mm²). After installing and switching ON, the sensor
flashes for 40 seconds.
If the rubber seal is damaged, the cable entry openings must be sealed with an M 16
or M 20 (at least IP 54) double seal cable gland.
5. Mounting
• Check all components for damage.
• Do not use the product if it is damaged.
• Select an appropriate mounting location, taking the reach and motion detection
into consideration.
22
Procedure for installing concealed power supply lead (Fig. 5.1)
Procedure for installing surface-mounted power supply lead (Fig. 5.2)
IS 3360, IS 3360 MX Highbay, IS 345, IS 345 Highbay
Procedure for installing concealed power supply lead (wall mounting) IS 3180 (Fig. 5.3)
For mounting the IS 3180 on the wall, a water drainage hole (Ø 5 mm drill bit) is
marked next to the rubber seal. This must be opened if necessary. (Fig. 5.3)
• Switch OFF power supply. (Fig. 5.1)
• Detach designer trim from sensor module.
• Disconnect sensor module from the connection module.
• Make DALI connection.
– Surface-mounted power supply lead (Fig. 5.4)
– Concealed power supply lead (Fig. 5.5)
• Insert fastening screws and mount connection module.
Detection zone / reach
IS 3360 (Fig. 5.6)
IS 3360 MX (Fig. 5.7)
Mounting height
Reach

14 m

10 m
9 m
14 m
6 m
16 m
2.8 m
18 m
IS 345 (Fig. 5.8)
IS 345 MX (Fig. 5.9)
Mounting height
Reach
14 m
30 m × 4
10 m
25 m × 4
8 m
20 m × 4
6 m
15 m × 4
4 m
10 m × 4
23