Honeywell
Commissioning:
Slowly
operating pressure is reached.
The pressure rise must not exceed
350 mbar/s.
A bypass line should be used for filling
(recommendation:
diameter).
Do not exceed the measuring range of
the gas meter even briefly.
A tightness test must then be carried
out.
4. Maintenance
INFORMATION!
Meters without an oil pump are maintenance-free.
NOTE!
Meters with an oil pump must be lubricated every 3 to 4 months.
For special gases such as propane or butane, or in difficult
operating conditions (e.g. full load operation or contaminated
gases), the lubrication intervals should be halved (every 1.5 – 2
months).
CAUTION!
Always keep the supply tank topped up with oil to prevent air
entering the pipe system. Use only fresh, clean oil. The supply tank
must be sealed tightly immediately after filling so that no dirt or
water can get into it.
NOTE!
Other non-resinous and non-acidic oils with a viscosity of
24arden24. 30 mm²/s at 20°C, solidification point lower than -
30°C, or equivalent oils may be used.
24
fill
the
system
12 mm
73018696g
until
the
pipe
Fig. 7 | Pushbutton oil pump
© Elster GmbH | All rights reserved. Subject to modification