5
Technical Data (excerpt)
The complete technical data and characteristic values (display
ranges, resolution, uncertainties etc.) can be found in the com-
plete operating instructions.
Ambient Conditions
Accuracy
–5 ... + 50 C
Operation
–20 ... + 60 C (without rechargeable
Storage
batteries)
Relative humidity
Max. 75%, no condensation allowed
Elevation
Max. 2000 m
Nominal Ranges of Use
Voltage U
N
Frequency f
N
Overall voltage range
Overall frequency range
Waveform
Temperature range
Supply voltage
Line impedance angle
Probe resistance
Overload Capacity
R
1200 V continuous
ISO
U
, U
600 V continuous
L-PE
L-N
RCD R
R
440 V continuous
E
F
Z
, Z
550 V (Limits the number of measurements
L-PE
L-N
and pause duration. If overload occurs, the
instrument is switched off by means of a
thermostatic switch.)
R
Electronic protection prevents switching on
LO
if interference voltage is present
Protection with
Fine-Wire Fuse
FF 3.15 A 10 s,
Fuses blow at > 5 A
Electrical Safety
Protection class
II per EN 61010-1
Nominal Voltage
230/400 V (300/500 V)
Test voltage
3.7 kV, 50 Hz
Measuring category
CAT III 600 V and CAT IV 300 V
Pollution degree
2
Fuses
L and N terminals
1 fuse link ea.
FF 3.15 A/500G 6.3 x 32 mm
Mechanical Design
Dimensions
W × L × D = 260 × 330 × 90 mm
Weight
approx. 2.7 kg with rechargeable batteries
Type of protection
Housing: IP40; test probes: IP40
per EN 60529
Data Interfaces
Type
USB type B for PC connection
Typ
USB type A for connecting a USB keyboard, bar-
code reader or RFID scanner
Gossen Metrawatt GmbH
0 ... + 40 C
120 V
(108 ... 132 V)
230 V
(196 ... 253 V)
400 V
(340 ... 440 V)
16 ⅔ Hz
(15.4 ... 18 Hz)
50 Hz
(49.5 ... 50.5 Hz)
60 Hz
(59.4 ... 60.6 Hz)
200 Hz
(190 ... 210 Hz)
400 Hz
(380 ... 420 Hz)
65 ... 550 V
15.4...420Hz
Sinusoidal
0 C ... + 40 C
8 ... 12 V
Corresponds to cos = 1 ... 0,95
< 50 k
6
Scope of Functions
PROFITEST MF ...
(article number)
Testing of residual current devices (RCDs)
U
measurement without tripping the RCCB
B
Tripping time measurement
Measurement of tripping current I
Selective, SRCDs, PRCDs, type G/R
AC/DC sensitive RCDs, types B and B+
DC sensitive RDC-DDs and RCMBs
Testing of insulation monitoring devices (IMDs)
Testing Residual Current Monitoring Devices (RCMs)
Testing for N-PE reversal
Measurements of loop impedance Z
Fuse table for systems without RCDs
Without tripping the RCD, fuse table
1)
15 mA measurement
Earth resistance R
(mains operation)
E
I/U measuring method (2/3-wire measuring method via
measuring adapter: 2-wire/2-wire + probe)
Earthing resistance R
(battery operation)
E
3 or 4-wire measuring method via PRO-RE adapter
Soil resistivity E (battery operation)
(4-wire measuring method via PRO-RE adapter)
Selective earthing resistance R
E
with 2-pole adapter, probe, earth electrode and current
clamp sensor (3-wire measuring method)
Selective earthing resistance R
E
with probe, earth electrode and current clamp sensor
(4-wire measuring method via PRO-RE adapter and current
clamp sensor)
Earth loop resistance R
(battery operation)
ESCHL
with 2 clamps (clip-on current transformer direct and clip-
on current transformer via PRO-RE/2 adapter)
Measurement of equipotential bonding R
automatic polarity reversal
Insulation resistance R
ISO
Variable or rising test voltage (ramp)
Voltage U
/ U
/ U
/ f
L-N
L-PE
N-PE
Special measurements
Current measurement with clamp I
Rotating Field Direction
Earth leakage resistance R
E(ISO)
Voltage drop (U)
Standing-surface insulation Z
ST
Meter start-up (kWh test)
Leakage current with PRO-AB adapter (IL)
Residual voltage test (Ures)
Intelligent ramp (ta + I)
Electric vehicles at charging stations (IEC 61851-1)
Documentation of fault simulations at PRCDs with the
PROFITEST PRCD adapter
Features
Selectable user interface language
Memory (database for up to 50,000 objects)
Automatic test sequences function
USB port type A (connection of USB keyboard/barcode
reader/RFID scanner)
USB port type B (data transmission)
PC database and report generating software IZYTRO-
3)
NIQ
Measuring category: CAT III 600V / CAT IV 300 V
DAkkS calibration certificate
1)
The so-called live measurement is only advisable if there is
no bias current within the system. Only suitable for motor
protection switches with small nominal current values.
As of firmware 3.4.4: 15 mA test current, only applies if RCD
is set with IΔN = 30 mA; otherwise test current = ½ · IΔN of
the pre-set RCDs
2)
currently available languages D, GB, I, F, E, P, NL, S, N, FIN,
CZ, PL
3)
IZYTRONIQ BUSINESS Starter (IZYTRONIQ CLOUD)
✓
✓
✓
✓
✓
✓
F
✓
✓
✓
✓
✓
✓
✓
—
✓
—
✓
✓
/ Z
L-PE
L-N
✓
✓
✓
✓
✓
✓
✓
✓
✓
—
✓
—
(mains operation)
✓
✓
(battery operation)
✓
—
✓
—
✓
✓
LO
✓
✓
✓
✓
✓
✓
, I
L
AMP
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
—
✓
—
✓
—
✓
✓
✓
—
2)
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
7