5.3.2. i
(F
ndicAtor light
Terminals "13 & 15". Output 24 V
beam status. After connection, the lamp will operate as follows:
Indicator light OFF = Automated system closed
Indicator light ON = Rod open
Indicator light flashing rapidly = Rod opening
Indicator light flashing slowly = Rod closing
The max. load that can be applied to these contacts cannot exceed 5 W.
When connecting the lamp, please observe the polarity of the terminals - terminal 13 is the positive pole.
5.3.3. r
l
(F
. 4)
od
ights
ig
Terminals "14 & 15". Output 24 V
(sold as a separate part). The luminous strip on the rod remarkably increases rod visibility. The behaviour of the strip is controlled
by parameter "G", see paragraph 9.
During viewing/programming phase of the operating parameters, the light on the rod flashes rapidly.
These terminals must only be used for the application of the luminous strip. Do not connect other devices.
When connecting the lamp, please observe the polarity of the terminals - terminal 14 is the positive pole.

5.4. CN4 TERMINAL BOARD

5.4.1. s
ynchronisAtion oF opposing bArriers
Terminals "16 & 22". These terminals are used to synchronise the movement of two barriers in applications with opposing bar-
riers. These terminals must be connected to the respective terminals on the second board, that is the terminals of both boards
must be jumper connected. Beside connecting these terminals, all pulse generators and safety devices must be connected
in parallel. The complete wiring diagram is shown in figure 7.
There is no need to connect terminal 23, fototest, in parallel.
The function parameters, including the operating logic and the pause time, of both control units must be set in the same
way.
The programming procedure must be carried out on both control units.
For applications with opposing barriers you are recommended to use an external receiver connected in parallel on both
boards for the operation with radio controls.
5.4.2. s
FsW (F
AFety devices
Terminals "17 & 22". NC contact. Connect, to these terminals, any obstacle detection device (i.e. photocells) which, by
opening the contact, commands the movement of the automated system. Use parameter "y", see paragraph 9, to select
the way in which the safety devices must operate: active only at closing or active both at closing and at opening. The status
of this input is signalled by LED FSW.
If no safety devices are connected, this input must be jumper-connected, LED FSW must be ON.
Several safety devices must be connected in series.
5.4.3. s
(F
. 5)
top
ig
Terminals "18 & 22". NC contact. Connect, to this terminal, any pulse generator (i.e. push-button, key selector) which, by opening
the contact, commands immediate stop of the automated system, and deactivation of any automatic functions.
After a STOP pulse, you need to send an OPEN pulse to resume normal operation of the automated system.
The status of this input is signalled by LED STOP.
The safety device of the door (NO contact always active) is already connected to these terminals. Do not remove the
connection.
Several STOP devices must be connected in series.
5.4.4. o
/ c
(F
pen
lose
ig
Terminals "19 & 22". NO contact. Connect, to these terminals, any pulse generator (i.e. push-button, key selector) which, by
closing the contact, commands opening or closing of the automated system. The behaviour of this input is controlled by
parameter "d", see paragraph 9. The status of this input is signalled by LED OP/CL.
Several pulse generators with this function must be connected in parallel.
5.4.5. o
(F
. 5)
pen
ig
Terminals "20 & 22". NO contact. Connect, to these terminals, any pulse generator (i.e. push-button, key selector) which, by
closing the contact, commands an opening of the beam. This input only controls the opening of the beam, therefore it has
no effect when the rod is open. The status of this input is signalled by LED OPEN.
Several pulse generators with this function must be connected in parallel.
5.4.6. c
(F
. 5)
lose
ig
. 4)
ig
max. 5 W. Connect, to these terminals, the lamp (if any) for the remote monitoring of the
max. 20 W. Connect, to these terminals, the luminous strip that must be positioned on the rod
(F
. 7)
ig
.6)
ig
. 5)
LYNX 08 24V