Download Print deze pagina

Victron energy EasySolar 12 1600 70-16 230V MPPT 100 50 Handleiding pagina 12

Advertenties

Beschikbare talen
  • NL

Beschikbare talen

  • DUTCH, pagina 33
4. INSTALLATION – inverter/charger
This product should be installed by a qualified electrician.
4.1 Location
The product must be installed in a dry and well-ventilated area, as close as possible to the
batteries. There should be a clear space of at least 10cm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
Reduced service life.
Reduced charging current.
Reduced peak capacity or shutdown of the inverter.
Never mount the appliance directly above the batteries.
The product is suitable for wall mounting. For mounting see appendix A.
The appliance can be mounted horizontally as well as vertically; vertical mounting is
preferable. The vertical position offers optimum cooling.
The interior of the product must remain accessible after installation.
Try and keep the distance between the product and the battery to a minimum in order to
minimize cable voltage losses.
For safety purposes, this product should be installed in a heat-resistant
environment if it is used with equipment where a substantial amount of power is
to be converted. You should prevent the presence of e.g. chemicals, synthetic
components, curtains or other textiles, etc., in the immediate vicinity.
4.2 Connection of Battery cables (see appendix A)
In order to fully utilize the full capacity of the product, batteries with sufficient capacity and
battery cables with sufficient cross section should be used. See table.
Preassembled
cable length 1.5 m
(mm
2)
Recommended
cross section (mm
2
)
1,5
1
 5 m
5  10 m
10
24/1600
12/1600
25
35
35
70
70
140

Advertenties

loading

Deze handleiding is ook geschikt voor:

Easysolar 24 1600 40-16 230v mppt 100 50