Download Inhoudsopgave Inhoud Print deze pagina
Inhoudsopgave

Advertenties

Beschikbare talen

Beschikbare talen

Digital Inverter
6

AIR PURGING

Airtight test
Before starting an airtight test, further tighten the spindle valves on the gas side and liquid side.
Pressurize the pipe with nitrogen gas charged from the service port to the design pressure (4.15 Mpa) to
conduct the airtight test.
After the airtight test is completed, evacuate the nitrogen gas.
Air Purge
With respect to the preservation of terrestrial environment, adopt "Vacuum pump" for air purge
(Evacuate air in the connecting pipes) when installing the unit.
• Do not discharge the refrigerant gas to the atmosphere to preserve the terrestrial environment.
• Use a vacuum pump to discharge the air (nitrogen, etc.) remained in the set. If the air remains,
the capacity may decrease.
For the vacuum pump, be sure to use one with backflow preventer so that the oil in the pump
does not backflow into the pipe of the air conditioner when the pump stops.
(If oil in the vacuum pump is put in an air conditioner including R410A, it may cause trouble on the
refrigeration cycle.)
Vacuum pump
As shown in the figure, connect the charge hose after the
manifold valve are closed completely.
Attach the connecting port of the charge hose with a
projection to push the valve core (setting pin) to the charge
Open handle Low fully.
Turn ON the vacuum pump (*1)
Loosen the flare nut of the packed valve (Gas side) a little to
check the air passes through. (*2)
Tighten the flare nut again.
Execute vacuuming until the compound pressure gauge
indicates –101kPa (–76cmHg). (*1)
Close handle Low completely.
Turn OFF the vacuum pump.
Leave the vacuum pump as it is for 1 or 2 minutes, and check
the indicator of the compound pressure gauge does not
Open fully the valve stem or the valve handle. (First, at liquid
side, then gas side)
port of the set.
return.
– 14 –
Outdoor Unit Installation Manual
(continued)
Disconnect the charge hose from the charge port.
Tighten valve and caps of the charge port surely.
*
1
Use the vacuum pump, vacuum pump adapter,
and gauge manifold correctly referring to the
manuals supplied with each tool before using
them.
Check that the vacuum pump oil is filled up to
the specified line of the oil gauge.
*
2
When air is not charged, check again whether
the connecting port of the discharge hose,
which has a projection to push the valve core, is
firmly connected to the charge port.
Compound pressure gauge
–101 kPa
(–76 cmHg)
Handle Lo
Charge hose
(For R410A only)
Charge port
(Valve core
Packed valve
(Setting pin))
at gas side
Toshiba XXXXXXX(<SanSerif1>X/X)
EN
Pressure gauge
Gauge manifold
valve
Handle Hi
(Keep fully
closed)
Charge hose
(For R410A only)
Vacuum pump
adapter for
counter-flow
prevention
(For R410A only)
Vacuum
pump
14-EN

Advertenties

Hoofdstukken

Inhoudsopgave
loading

Deze handleiding is ook geschikt voor:

Rav-sm1603atz-eRav-sm1603atzg-e

Inhoudsopgave