Download Inhoudsopgave Inhoud Print deze pagina

Electrode Setting; Burner Start-Up Cycle - Riello Burners 40 G10 Installatie-, Gebruiks- En Onderhoudsvoorschriften

Inhoudsopgave

Advertenties

Beschikbare talen

Beschikbare talen

It is important to take account of the fact that the air
output of the fan differs according to whether the
burner has its metal cover fitted or not.
Therefore we recommended to proceed as follows:
– adjust the air damper as indicated in the schedule (4);
– mount the cover, simply by means of the upper
screw;
– check smoke number;
– should it become necessary to modify the air out-
put, remove the cover by loosening the screw,
adjust the air damper, remount the cover and finally
recheck the smoke number.
NOTE: When the burner works at a firing rate
higher than 9 kg/h remove the panel fitted
inside the metal cover. (See figure).

ELECTRODE SETTING

Attention:
Before assembling or removing the nozzle, loosen
the screw (A) and move the electrodes ahead.

BURNER START-UP CYCLE

Normal
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
2351
All manuals and user guides at all-guides.com
4 ±
0.3 mm
D5288
~
12s
MOVE THE ELECTRODE
HOLDER BACKWARDS TO
THE END
A
Lock-out, due to light-failure
~
12s
9
GB
PANEL
D5287
4.5 ±
0.5 mm
~
5s
D5229

Advertenties

Inhoudsopgave
loading

Deze handleiding is ook geschikt voor:

3746412

Inhoudsopgave