Elektrische installatie
6
UL-conforme installatie
6.4
UL-conforme installatie
6.4.1
Power terminals
6.4.2
Short circuit current rating
6.4.3
Branch circuit protection
Model
PHC21A-
A022M1-...A-00/..
PHC21A-
A040M1-...A-00/..
PHC21A-
A075M1-...A-00/..
48
Technische handleiding – MOVIPRO
AANWIJZING
Ongeacht de taal van dit document, wordt het volgende hoofdstuk vanwege de UL-
vereisten altijd in het Engels afgedrukt.
Use 75 °C copper wire only.
®
•
MOVIPRO
is suitable for use on a circuit capable of delivering not more than
200,000 rms symmetrical amperes when protected by fuses and circuit breakers
as described in the tables below.
®
•
MOVIPRO
is suitable for use on a circuit capable of delivering not more than
65,000 rms symmetrical amperes when protected by ABB and Rockwell Type E
Combination Motor controllers as described in the tables below.
Max. voltage is limited to 500 V.
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
®
For MOVIPRO
use branch circuit protection as follows:
Three Phase 380 V – 500 V Voltage Range
SCCR:
200 kA/500 V
When protected by:
When protected by:
Non Semiconduc-
Inverse-Time Cir-
tor Fuses (currents
are maximum valu-
es)
40 A/600 V
50 A max/500 V min
40 A/600 V
50 A max/500 V min
40 A/600 V
50 A max/500 V min
®
PHC2.A-A..M1-..2A-C5
SCCR:
SCCR: 65 kA/480 V
200 kA/500 V
When protected
Type E Combinationen Motor Controller
cuit Breaker
ABB, Model
MS132‑6.3 Ra-
ted 480 V, 3 HP
ABB, Model
MS132‑10 Ra-
ted 480 V, 5 HP
ABB, Model
MS132‑16 Ra-
ted 480 V, 10 HP
SCCR: 65 kA/460 V
When protected by:
1)
by:
Rockwell Automati-
on, Model
140M‑C2E-B63 Ra-
ted 460 V, 5 HP
Rockwell Automati-
on, Model
140M‑C2E-C10 Ra-
ted 460 V, 7.5 HP
Rockwell Automati-
on, Model
140M‑D8E-C16 Ra-
ted 460 V, 10 HP