6 De frequentieomvormer programmeren
AN-50 Terminal 42 Output
Option:
[0] *
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor Current
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
[107]
Speed
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
6
[115]
Ext. Closed Loop 3
[130]
Output freq. 4-20mA
[131]
Reference 4-20mA
[132]
Feedback 4-20mA
[133]
Motor cur. 4-20mA
[134]
Torq.% lim 4-20 mA
[135]
Torq.% nom 4-20mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[139]
Bus ctrl.
[140]
Bus ctrl. 4-20 mA
[141]
Bus ctrl t.o.
[142]
Bus ctrl t.o. 4-20mA
[143]
Ext. CL 1 4-20mA
[144]
Ext. CL 2 4-20mA
[145]
Ext. CL 3 4-20mA
NB!
De minimumreferentie wordt ingesteld via par. F-52
Maximum Reference
ingesteld via par. F-53
AN-51 Terminal 42 Output Min Scale
Range:
0.00 %*
[0.00 - 200.00 %]
AN-52 Terminal 42 Output Max Scale
Range:
100.00 %*
[0.00 - 200.00 %]
VOORBEELD 1:
Gegevenswaarde = UITGANGSFREQUENTIE, bereik = 0-100 Hz
Vereiste bereik voor uitgang = 0-50 Hz
Een uitgangssignaal van 0 of 4 mA is vereist bij 0 Hz (0% van bereik) – stel par. AN-51
Een uitgangssignaal van 20 mA is vereist bij 50 Hz (50% van bereik) – stel par. AN-52
74
Functie:
Selecteer de functie voor klem 42 als een analoge stroomuitgang.
Minimum Reference
en par. CL-13
Maximum Reference/Feedb.
en par. CL-14
Functie:
Functie:
MG.11.L2.10 – ADAP-KOOL
®
ADAP-KOOL
Drive Bedieningshandleiding
Minimum Reference/Feedb.
– de maximumreferentie wordt
.
Terminal 42 Output Min Scale
in op 0%
Terminal 42 Output Max Scale
in op 50%
®
Drive