Download Print deze pagina

LG ESS Home 10 Installatiehandleiding pagina 32

Verberg thumbnails Zie ook voor ESS Home 10:

Advertenties

Beschikbare talen

Beschikbare talen

32
Installation
Grid Connections
To use or sell the generated energy through grid connection, you should connect grid to this product.
This product converts DC electricity generated from PV array to AC electricity. The generated energy
can be sold to the electric utility or used for the household appliance.
WARNING
Make sure the AC circuit breaker, PV switch and DC circuit breaker of the battery are disconnected
2
before starting electrical cable connections. .
NOTE
y AC circuit breaker must be the current ratings of 32A.
y This product can cause current with a DC component. Where a Residual Current-operated
protective (RCD) or monitoring (RCM) device is used for protection in case of direct or indirect
contact, only an RCD or RCM of Type A (or type B) is allowed on the supply side of this product.
y Connect the equipment grounding before connecting the AC wires to the grid.
Before making a grid connection, other end of an AC cable should be connected to an AC circuit
breaker on the distribution box.
A
Check the components of grid cable
plug which is supplied in the product
package.
1. Cable gland
2. Rubber seal
3. Housing
4. Contact carriers

Advertenties

loading

Deze handleiding is ook geschikt voor:

Ess home 8D010ke1n211D008ke1n211