Now complete the remaining zones. To do this, repeat the following
steps, working towards the central extract unit.
Select the exhaust vent with the highest flow rate.
6
Adjust the flow rate through the exhaust vent in step
7
fine-tuning the feed-through component (e.g. using the arrow keys
on the iAV control valve).
Measure any remaining vents within the current zone and fine-
8
tune them using the exhaust vent. Work from highest to lowest
flow rate.
Exit configuration mode by pressing 'HIGH' on the iAV Control valve
9
or on the IQ-unit.
ENGLISH