Download Inhoudsopgave Inhoud Print deze pagina

Mounting The Product; Leaking Product - afriso Flow-Control 3/K Gebruiksaanwijzing

Inhoudsopgave

Advertenties

Beschikbare talen

Beschikbare talen

5.3

Mounting the product

LEAKING PRODUCT

Verify that you use a screwed pipe connection as per DIN 2353 with cylindri-
cal thread (G thread) and seal the screwed pipe connection with a flat gasket
or with suitable glue. Do not use Teflon tape or hemp.
Failure to follow these instructions can result in equipment damage.
INOPERABLE PRODUCT
Verify that you do not interchange the burner hoses for the flow and return
lines.
Failure to follow these instructions can result in equipment damage.
 Verify compliance with the specified ambient conditions.
 Verify that the float housing points vertically to the top.
 Verify that an oil filter is installed in the supply line upstream of the prod-
uct.
Mounting
NOTICE
NOTICE
Flow-Control
EN
14

Advertenties

Inhoudsopgave
loading

Gerelateerde Producten voor afriso Flow-Control 3/K

Deze handleiding is ook geschikt voor:

Flow-control 3/k htFlow-control series

Inhoudsopgave