6. TECHNICAL SPECIFICATIONS / DECLARATION OF CONFORMITY

12/850
6.1
Phoenix
1)
Output power
: @ Ta=25°C
Short circuit output current
Output voltage
Output frequency
Output waveform
Admissible cos ϕ of load
Input voltage :
Maximum input ripple voltage
Efficiency
No load power consumption at nominal
input voltage
No load power consumption at nominal
input voltage in automatic standby mode
Automatic standby threshold
Operating temperature range (ambient)
Protections against
Error indications (by preprogrammed
blinking sequences of the red LED)
Other indications
DC input connection
AC output connection
Enclosure body size (l x h x w)
Protection class
Inverter weight
The inverter complies with the following
standards :
Note : the given specifications are subject to change without notice
1)
Measured with resistive load

TECHNICAL DATA

Pnom
P30
Psurge
Nominal
Range (static)
Range @ 850VA
Maximum
@ Pnom
Short circuit, overload, high temperature, low battery
EN50081-1 Generic Emissions Standard
EN50082-1 Generic Immunity Standard
EN60950
EN60742

Phoenix 12/850

850VA
1000VA
1800VA
≈ 8A
230VAC ± 1%
50Hz ± 0.05%
True sinewave (THD < 5% @ Pnom)
0.5 – 1
12VDC
10.5 – 16VDC
9.7 – 16VDC
≈ 1.3VACrms
92%
83%
< 7.5W
< 1.5W
Pout = 5W
0 .. 40 °C
voltage and high input ripple voltage
Short circuit/overload, high temperature, high/low
battery voltage and high input ripple voltage
Overload (red LED)
AC Present (blue LED)
two wires, length 1.5 meters, area ∅ 25mm²
IEC320 type AC outlet
355 x 105 x 206mm (without mounting brackets)
IP20
10.5 kg
Safety Standard
Transformer Standard
17