PROBLEM : 'Inverter temperature too high. Cooling down' error keeps on appearing
Possible cause :
Airflow around the inverter is obstructed
Too high ambient temperature
Note : Don't turn off the inverter when it's operating in an 'Inverter temperature too high. Cooling
down' error. The inverter needs this error time to cool down.
PROBLEM : 'Too high input ripple voltage' error keeps on appearing
Possible cause :
Input voltage ripple is too large caused by poor
inverter installation
PROBLEM : Inverter jumps between continuous mode and pulsed ASB mode all the time
Possible cause :
Connected load is not compensated or the ratio
between inrush current and continuous current
is too large.
If none of the above remedies will help solve the problem you encounter, it's best to contact your
local Victron Energy distributor for further help and/or possible repair of your inverter. Do not try to
repair the inverter yourself, there are dangerous high voltages present inside. Attempts to repair
and/or modify the inverter will directly void your warranty.

4. WARRANTY

Victron Energy warrants this inverter to be free from defects in workmanship or materials for 24
months from the date of purchase. During this period Victron Energy will repair the defective
inverter free of charge. Victron Energy is not responsible for any costs of the transport of this
inverter.
This warranty is void if the inverter has suffered any physical damage or alteration, either internally
or externally, and does not cover damage arising from improper use, attempting to operate the
inverter with excessive power consumption requirements, or from use in an unsuitable
environment.
This warranty will not apply where the product has been misused, neglected, improperly installed
or repaired by anyone other than Victron Energy. Victron Energy is not responsible for any loss,
damage or costs arising from improper use, use in an unsuitable environment, improper installing
of the inverter and inverter malfunctioning.
14
Remedy :
Make sure there is at least 10 centimeters of
clearance around the inverter. Remove any
items placed on or over the inverter. Keep the
inverter away from direct sunlight or heat
producing equipment
Move the inverter to a cooler place or provide
additional cooling by an external fan
Remedy :
Reduce load, enlarge battery capacity, make
sure the DC wires are not extended too long (<3
meters) and that sufficient wire gauge is used
(>1.5x the standard equipped wire gauge),
check eventual generators/dynamos/high ripple
chargers which are connected to the same DC
system.
Remedy :
Connect an additional load to the output.