SATEL
SATEL Sp. z o.o. • ul. Budowlanych 66 • 80-298 Gdańsk • POLAND
The National Technical Assessment CNBOP-PIB-KOT-2021/0268-1002 (first edition of
Essential characteristics
of the construction product
for the intended use
Design requirements
Labelling requirements
Signaling by the remote alarm indicator
Visibility of the remote alarm indicator
Resistance to cold
Resistance to dry heat
Resistance to sulfur dioxide corrosion
Resistance to impact
Resistance to steady damp heat
Protection against the ingress of foreign bodies
provided by the enclosure
Immunity to electrostatic discharge
RF electromagnetic field immunity
Immunity to electrical fast transients/bursts
Surge immunity
Immunity to conducted disturbances inducted by
radio frequency fields
Certificate No. 063-UWB-0366
Name and type: WZ-110 type remote alarm indicator
Intended use: Fire safety – devices for use in buildings.
WZ-110
21
30.08.2021)
Declared
performance
pass
pt. 3.3 of the National Technical Assessment
pass
pt. 3.1 of the National Technical Assessment
pass
The remote alarm indicator LEDs flash to signal
the alarm condition of the detectors connected to
The remote alarm indicator powered from the
pass
detector, with background illuminance up to 500 lx,
is visible from a distance of 6 m directly in front of
pass
pass
pass
SO2 concentration: 25 ppm (± 5 ppm)
pass
pass
pass
pass
pass
pass
pass
pass
Notes
it.
the indicator.
Temperature: -10°C (± 3°C)
Endurance: 16 hours
Temperature: +55 (± 2°C)
Endurance: 16 hours
Temperature: +25 (± 2°C)
Relative humidity: 93% (± 3%)
Endurance: 504 hours (21 days)
Impact energy: 0.5 J (±0.04J)
Number of impacts per point: 3
Temperature: +40°C (± 2°C)
Relative humidity: 93% (± 3%)
Endurance: 96 hours (4 days)
IP 3X
PN-EN 50130-4:2012 + A1:2015-03
PN-EN 50130-4:2012 + A1:2015-03
PN-EN 50130-4:2012 + A1:2015-03
PN-EN 50130-4:2012 + A1:2015-03
PN-EN 50130-4:2012 + A1:2015-03
5