Sensepoint XCD RTD Technische handleiding
Certificate:
2404330
Project:
2404330
Ex d ia IIC;
Class I, Div. 2, Groups B, C and D;
Sensepoint Toxic sensor head p/n 2106B18xx(Toxic gasses & Oxygen), Input rated 32 VDC, 0.9 watts max.
Temperature code T4 when installed per control drawing 3001EC088.
Note: XX may be 00 to 02, 05 to 07, 10 to 18, 20 to 22 and 30 depending on which gas cell is installed in the
Sensepoint Toxic sensor head.
CLASS 4828 82
Class I, Zone 1, AEx d IIB+H2;
Sensepoint XCD/RTD Stationary Toxic gasses & Oxygen Gas Transmitter, Input rated 16 to 32 VDC, 3 watts
max. Temperature code T4, Relay ratings 3X5A@250VAC, with or without RS-485 Module, Tamb -40 Deg.
C to +65 Deg. C. For use with integral Sensepoint Toxic/oxygen sensor head p/n 2106B18xx or with remote
junction box fitted with Sensepoint Toxic/oxygen sensor head p/n 2106B18xx when installed per control
drawing 3001EC088.
Note: XX may be 00 to 02, 05 to 07, 10 to 18, 20 to 22 and 30 depending on which gas cell is installed in the
Sensepoint Toxic sensor head.
Class I, Zone 1, AEx d ia IIC Gb;
Class I, Div. 2, Groups B, C and D;
Sensepoint Toxic sensor head p/n 2106B18xx(Toxic gasses & Oxygen), Input rated 32 VDC, 0.9 watts max.
Temperature code T4 when installed per control drawing 3001EC088.
Note: XX may be 00 to 02, 05 to 07, 10 to 18, 20 to 22 and 30 depending on which gas cell is installed in the
Sensepoint Toxic sensor head.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91 - General Requirements – Canadian Electrical Code, Part II
DQD 507 Rev. 2009-09-01
SPXCDHMRTEN Uitgave 3_10-2013
Master Contract:
Date Issued:
Page: 2
72
246287
July 22, 2011