Placing the concentric channel system

The concentric channel system consists of three parts:
the channels itself, the transit through the roof or the
wall and the outflow.
Instructions for placing the outflow
The outflow of the pipe system can be placed on top of
the roof or against the side wall of the house.
Outflow on top of the roof
When placing the outflow on top of the roof, make sure
that there is a distance of at least 50 cm between the
outflow and the edges of the roof, with the exception of
a possible existing ridge. You must also take the place
of the outflow into account in relation to the existing
ventilation openings, movable windows and combustion
air supply provisions. Please consult the national and
local requirements.
Outflow into the wall
When placing the outflow into the side wall, make sure
that there is distance of at least 50 cm between the
outflow and the corners of the building, eaves, gutters,
balconies and etceteras. You need not have this distance
28
28
when the outflow runs to at least the front side of the
overhanging part.
You must also take into consideration the place of the
outflow in relation to the existing ventilation openings,
movable windows and combustion air supply provisions.
Please consult the national and local requirements.

Placing possibilities of the pipe system

To make the hearth turnable you always need the 4175
WANDERS turning pipe; the first vertical pipe A. The
total length of the pipe system must never be more than
10 metres excluding the passage through the wall and
outer wall. A 90° square angle counts as a length of
2 metres. A 45° turn counts as a length of 1 metre.
For the combined flue tube and combustion air supply
you must apply one of the following possibilities of the
WANDERS concentric pipe systems: with wall duct, with
roof duct, or with roof duct with bend. When leading the
pipe through the outer wall you must always make it
1 metre vertical before going through the outer wall.
Installation through the outer wall
Always allow 1 metre vertical before passing through the
outer wall.
Kind of gas length of duct A length of duct B Sealing
(min. – max.)
Natural gas 1,0 – 3,0 m
Propane
1,5 – 3,0 m
All measures are excluding the length of the transit
through the wall.
(min. – max.)
0 – 3,0 m
No
0 – 3,0 m
No