Installation, operating and maintenance instructions

Functional control

Preparation before function check - Test run settings
Before the function check, the pre-filters must be cleaned (see page 7) and the system pressure
needs to be at least 0.8 bar for the function check to be made.
to continuous operation by adjusting "Days left" to 1day
Set the TTM NoXygen
®
MOVEO
Progv 2.16
Days left
0/30
MOVEO
Set the TTM NoXygen
to
®
continuous operation by
pressing
until "Days left"
appears on the display.
1. Cleaning prefilters
See page 7-8.
2. Expansion vessel control
Check that the expansion vessel is correctly adjusted with cor-
rect pre-pressure and that there is free expansion volume. The
TTM NoXygen
M650 requires at least 6 litres of free expansion
®
space. If it is suspected that the expansion space is too small,
install TTM Offset expansion vessel (art.no. 518853).
3. Pressure sensor control
Check that the "Pint" pressure on the TTM NoXygen
in idle mode is between minimum 0.8 bar and maximum 5.0
bar (the unit will not start if the pressure is below 0.8 bar, see
troubleshooting action 1.1). If the pressure on the display does
Pressure
Time
1.0 bar
150 s
2.0 bar
140 s
3.0 bar
130 s
4.0 bar
120 s
5.0 bar
110 s
TTM Energiprodukter AB
Slöjdaregatan 1 | 393 66 Kalmar | Sweden | Tel. + 46 480-41 77 40 | info@ttmenergi.se | www.ttmenergi.se
For latest updates visit www.ttmenergi.se.
M650
®
MOVEO
Settings
MOVEO
MOVEO
Then press simultaneously
+
to activate
"Settings".
display
®
Blue
control hose
Transparent
bottle
filled with
water.
TTM NoXygen
Settings
Days left
0d
MOVEO
Then press simultaneously
+
to activate
editing mode.
not match the system pressure, see troubleshooting action 7.
Also check that the "Pint" reaches at least -0.7 while the pump
is running. If not, see troubleshooting action 2.
4. Operating cycle time control
The time from pump start to pump start should not exceed the
recommendations in the table below. Long cycle times
indicate clogging of filters or flow restrictors.
See troubleshooting action 3.
5. Leakage control
Check that no fluid is leaking from the blue control hose, when
the "Pint" pressure is equal to the system pressure of the plant,
in case of leakage, contact TTM. Check that no system fluid
is leaking from any of the connections to the pump or vacuum
TTM MAG 54
Magnetite
separator
®
Degasser
MOVEO
Settings
Days left
MOVEO
MOVEO
Press
to set "Days left = 1d".
Confirm by saving the setting
with
.
Shut off valve
Shut off valve
Shut off valve
Balancing valve
2024-01
MOVEO
1d
MOVEO
9