Maintenance

TTM NoXygen
EN
Installation, operating and maintenance instructions

Cleaning the filter basket of the inlet valve

WARNING
!
If TTM NoXygen
is installed in a heating system then hot
®
pressurised system fluid may leak out when the protec-
tive cap B is unscrewed.
Before starting cleaning of the inlet valve,
ensure that:
1. The inlet and outlet valve handle A is in the closed position.
2. The TTM NoXygen
is turned off or the the main power is isolated.
®
Disassembly of the inlet valve
3. Loosen the protective cap B on the inlet valve with a spanner.
Let the gasket remain in the protective cover.
4. Remove the filter basket C and clean it and the protective
cap with water.
Mounting the strainer basket
5. Replace the strainer basket C in the inlet valve. Ensure that the filter
basket is entirely submerged and sits evenly with the valve body.
6. Make sure that the protective cap gasket is correctly located. Screw
the protective cap B on the inlet valve with a spanner.
7. Turn the inlet and outlet valve handle A to the open position.

Maintenance of TTM MAG 54

Strong magnetic
Can affect
field
pacemaker/ICD
TTM MAG 54 should be inspected and cleaned regularly, at least
twice per year. The intervals depend on the quantity of particles and
magnesite in the system fluid. If you know the system fluid is very dirty,
the filter should be inspected and cleaned more often. One sign that
TTM MAG 54 requires cleaning is, for example, that TTM NoXygen
runs for long intervals exceeding 3 minutes "pump start to pump start"
(see Operating and maintenance instructions for TTM NoXygen
Cleaning the magnetite trap
1. Switch off both TTM NoXygen
main power.
2. Close both inlet valves 1
(see image 2).
3. Install hose 6 on the hose connector.
3. Unscrew the magnet insert 2.
4. Empty the particle trap by opening
the drain valve 3. Leave the water to run
until the housing is empty or until the fluid
is clear and without contaminants.
5. Close the drain valve 3 and screw the
magnet insert back in place 2.
6. Open both inlet valves 1
(see image 2).
7. Start TTM NoXygen
.
®
TTM Energiprodukter AB
Slöjdaregatan 1 | 393 66 Kalmar | Sweden | Tel. + 46 480-41 77 40 | info@ttmenergi.se | www.ttmenergi.se
For latest updates visit www.ttmenergi.se.
M650
®
Also be aware that the
magnet may interfere with
electronic equipment and
Risk of pinching
pacemakers.
).
®
and the
®
3
6
(Image 1)
Inlet
Outlet
Inlopp
Utlopp
A
A
Inlet
Outlet
Inlopp
Utlopp
A
A
Cleaning the particle filter
®
1. Switch off both TTM NoXygen
power.
2. Close both inlet valves 1.
3. Install hose 6 on the hose connector.
4. Empty the magnetite filter by opening the
drain valve 3. Leave the water to run until the
housing is empty of water.
5. Unscrew the bottom insert 4.
6. Unscrew the magnet insert 2 (see image 1).
7. Clean the particle filter 5 and other parts
with lukewarm water.
8. Screw the magnet insert back in place 2.
2
9. Ensure the particle filter 5 and the O-ring
are correctly installed and screw the bottom
insert 4 into the housing.
10. Close the drain valve 3.
11. Open both inlet valves 1.
12. Start TTM NoXygen
B
C
and the main
®
1
(Image 2)
.
®
2024-01
A
1
5
4
3
6
7