Installation
Pipe connection
•
TTM NoXygen
is fitted with a ½" internally threaded connection.
®
The connection is made with a steel-braided hose to system's return
conduit in front of the pump and exchanger.
•
Connection to the system should always be made at the top of the
pipework. When connecting on the bottom of the pipe, TTM MAG 54
or TTM MAG 76 filters should be installed before TTM NoXygen
on the incoming pipe. Installation of a filter on the incoming pipework
is recommended for all other connections.
•
The pipe to the degasser must be fitted with shut-off valves. The
distance between connection points shall be at least 300 mm. The
TTM NoXygen
M650 is only allowed to be connected to waterborne
®
heating or cooling systems without chemical additives (Fig. 1 och 2).
Connect tap water
Connect the water supply to the right 1/2" connection and provide the
wire with a shut-off valve (Fig. 1 and 2).
Drip Tray
The drip tray's ½" connection is connected to the floor drain (Fig. 3).
Mounting
Adjust the mounting screws on TTM NoXygen's feet so that it stands
horizontally (Fig. 4).
Electrical Connection
TTM NoXygen
is connected by plugging in the wall plug to an earthed
®
socket 1-230 V, 50 Hz Alternatively, it can be connected to a fixed
earthed connection with a circuit breaker. The electrical unit should be
equipped with a residual current device.
Connection to External Monitoring (DUC)
The TTM NoXygen
M650 can be integrated in the building automation
®
system with MODBUS RTU via RS485. The switching pin
is mounted externally on the right side of the device (Fig. 5).
Fig. 5
Commissioning
and operation
1. Starting TTM NoXygen
4
M650
®
Main flow hot
circulation water
MOVEO
T Pint:
1.2 bar
®
0
MOVEO
Press
twice to start the TTM NoXygen. When the green LED lights up, the unit is now in operation.
Slöjdaregatan 1 | 393 66 Kalmar | Sweden | Tel. + 46 480-41 77 40 | info@ttmenergi.se | www.ttmenergi.se
Fig. 1
Main flow hot
circulation water
®
≥300
Fig. 2.
Tap water
Fig. 3
Fig. 4
Adjust the adjusting screws at the
floor installation.
+
MOVEO
Start?