Maintenance
TTM NoXygen
EN
Installation, operating and maintenance instructions
Maintenance of TTM MAG 76
Magnetic field
TTM MAG 76 must be checked and cleaned regularly – at least twice per
year. The interval depends on the quantity of dirt and magnetite in the system
fluid. One sign that TTM MAG 76 requires cleaning is, for example, that TTM
NoXygen
runs for long intervals exceeding 3 minutes "pump start to pump
®
start".
Note: Copper paste/silicone grease must be applied to the thread of the
clamp ring once per year or every time the filter is opened.
1. Switch off TTM NoXygen
.
®
2. Shut off the shut off valves on the inlet to
TTM MAG 76 and the inlet to TTM NoXygen
3. Place a container under the drain valve or connect a hose to it.
4. Open the drain valve.
5. Undo the clamp ring and lift out the magnetic rod and filter cartridge.
6. Wipe off the black magnetite that is collected on the magnetic rod.
7. Clean the filter cartridge or replace it if it is damaged.
8. Refit the filter cartridge and magnetic rod and fix into place with the
clamp ring. Grease the clamp ring threads with copper paste/silicone
grease before tightening.
Installation of TTM MAG 54 and TTM MAG 76
Art. no: 514428
The TTM MAG 54/76 mounts directly on the TTM NoXygen
to the system via 1/2" female pipe thread and it is recommended to use a flexible hose.
1. Fit the supplied clamping ring coupling.
2. Connect the flat end of the TTM MAG 54/76 to the clamping ring coupling.
3. Mount the TTM MAG 54/76 directly on the shut-off valve on the inlet of the
TTM NoXygen
.
®
Installation of TTM Offset 600
Art.no: 518853
1. Close the shut-off valve to the system.
2. Remove the protective cover on the drain valve.
3. Open the drain valve (the spindle located on the side) and let the
water drain out.
4. Remove the black protective cover and take off the valve cap to
air valve.
5. Adjust the rubber lock pre-pressure so that this corresponds to
70-80% of the system pressure by releasing or replenishing air
through the air nipple.
6. Close the drain valve and reinstall the valve bonnet and
protective cover.
7. Reassemble the protective cover to the drain valve.
8. Open the shut-off valve to the system.
8
C625
®
.
®
Art.no: 506188
inlet valve. It is connected
®
Slöjdaregatan 1 | 393 66 Kalmar | Sweden | Tel. + 46 480-41 77 40 | info@ttmenergi.se | www.ttmenergi.se
DN15 (1/2")
DN15 (1/2")
Drainage
Avtappning
1. Magnetic rod
2. Replaceable filter cartridge
Article no: u2001217
TTM MAG 54
Magnetite filter
TTM NoXygen
®
Degasser
TTM Offset
Equalisation
vessel
IN
Ø140
Ø75
1
2
DN15 (1/2")
OUT
UT
TTM GeniX
Pressurization unit
TTM Energiprodukter AB
For latest updates visit www.ttmenergi.se.
2024-06
Main pump
®