TTM NoXygen
EN
Installation, operating and maintenance instructions
Display
Factory reset
•
Unplug the unit. When in a non-powered state, press
the left and down arrows simultaneously as you
reconnect the plug.
•
Hold until "OFF NOW" is shown on the display.
•
Release the arrows and unplug the unit again.
•
Reconnect NoXygen with the contact.
•
NoXygen is now factory reset.
Alarm list
#2 Pmin:
The pressure in the connection point is
too low. Increase the pressure up to at
least 0.8 bar.
#4 Pint > SafetyP:
The system pressure has exceed the
maximum permissible pressure
"SafetyP".
#5 Max Tcycle:
The cycle time has been more than
3 minutes. This indicates that the
incoming flow is blocked in the filter or
the flow restrictor.
Pos
01>2 1021 14:37
Position in
alarm list
Alarm number
Alarm date (mm-dd)
Alarm time (hh-mm)
Operating modes
Fast degassing/Intensive degassing
For new installations and system fluid replacement, fast
degassing is recommended. Fast degassing means that the
TTM NoXygen
runs continuously between 00:00 on Monday
®
and 23:59 on Friday.
The preset value is 30 days of fast degassing, which in most
cases is sufficient to degass the system. In large systems or in
systems with many air pockets, longer time may be needed to
remove all air. It is possible to increase the number of days in
fast degassing mode up to 90 days.
6
C625
®
MOVEO
Slöjdaregatan 1 | 393 66 Kalmar | Sweden | Tel. + 46 480-41 77 40 | info@ttmenergi.se | www.ttmenergi.se
Red LED indicates
alarm.
Green LED indicates
that the unit is in
operation.
Arrows right/left,
up/down.
Explanation of display messages
Displays the current pressure inside the vacuum
Pint
chamber of the NoXygen
Date
Setting the date "yy-mm-dd".
Clock
Setting of the clock "hh-mm-ss".
The time when TTM NoXygen
Tstart
timer operation.
Toperat
How many hours the TTM NoXygen
maintenance degassing per day.
Days left
How many days of fast degassing mode
remains before the TTM NoXygen
maintenance degassing.
Modbus ID TTM NoXygen
Pmin
Setting the minimum permissible system
pressure (Alarm limit).
Setting to avoid the release of the safety valve
SafetyP
(Alarm limit).
nbpumps
Number of pump starts.
Maintenance degassing
When the system is degassed, there is very little air left in the
system and it only costs money to keep the degasser active
around the clock and increases wear on the unit.
There is always some air leakage into the system that needs
to be taken care of. During maintenance degassing, the TTM
NoXygen
only runs for a few hours per day, which is sufficient
®
to take care of the system air leakage. The number of hours
per day needed to maintain low gas levels is shown in the table
below.
Recommended operating time per day
System volume
5 000 litres
10 000 litres
15 000 litres
20 000 litres
25 000 litres
For latest updates visit www.ttmenergi.se.
2024-06
MOVEO
TTM NoXygen
®
PROGRV 2.16
Enter
.
®
shall start in
®
shall run in
®
enters the
®
address in modbus system.
®
Operating time
1 hour
2 hours
3 hours
4 hours
5 hours
TTM Energiprodukter AB