EN: Installation instructions
Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
EN 54-14 standard and local regulations.
To install a detector:
Caution:
Polarity requirements for detectors vary. See
individual detector specifications for more information.
Insert the detector head into the mounting base and rotate it
clockwise until it clicks into place (Figure 1).
The detector may be locked into the mounting base if required.
To do this, remove the locking tab before installation
(Figure 2).
After installation, ensure that the detector communicates with
the control panel. If the detector does not communicate with
the control panel, check that duplicate addresses have not
been assigned.
Always test detectors after installation.
To remove a locked detector:
1.
Insert a small screwdriver into the locking tab slot
(Figure 3).
2.
Press and rotate the detector anticlockwise.
Addressing
Each detector must be assigned an address from 1 to 128.
Use the rotary dial marked 0 to 12 to set the tens and
hundreds part of the address, and the rotary dial marked 0 to 9
for the remaining digits. See Figure 6 for sample address
settings.
Note:
To overcome the mechanical effects of shipping and
storage, we recommend that you first rotate each dial counter-
clockwise (to the 0 position) and then clockwise (to the dial's
maximum position) before setting the required address.
Status indications
LED indicator
Each detector includes 1 or 2 red LEDs for alarm indication, as
shown in the table below.
Detector
LEDs
Alarm indication
DP2061N
2
Constant LED
DP2061T
DP2061
DT2063
DP2071
1
Constant LED
DT2073
Seven-segment display
In addition to the standard LED alarm indication, the DP2071
and DT2073 detectors include a seven-segment display with
the following status indications:
2 / 16
Indication
Description
A
Alarm
P
Pre-alarm
C
Detector maintenance
F
Detector fault
E
Error (for example, duplicated address)
O
Soak test
o
Detector disabled
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Diagnostic and sensitivity test
On detectors with a seven-segment display, a diagnostic and
sensitivity test is available.
The test is initiated by holding a magnet to the integral reed
switch, marked by the word TEST on the detector housing. The
test results (device address and current analogue value) are
indicated on the seven-segment display.
Replacing the optical chamber
To replace the optical chamber:
1.
Remove the detector head from the mounting base.
2.
Remove the detector cap by inserting a screwdriver and
lifting (Figure 4).
3.
Remove the used optical chamber from the detector.
4.
Clean the replacement optical chamber using compressed
air and insert it into the detector (Figure 5).
5.
Replace the detector cap and install the detector head into
the mounting base.
6.
Test the detector according to local regulations and verify
that it signals an alarm at the control panel.
To clean the optical chamber, follow the above instructions for
removal and use compressed air to clear the dust.
Caution:
After replacing or cleaning the optical chamber,
check that the analogue value of the detector at the control
panel is within normal limits for the detector type and
environmental conditions.
Specifications
DP2061N
DP2061T
Operating voltage
17 to 28 VDC
Current consumption
350 µA
in standby
Current consumption
4 mA
in alarm
Remote alarm output
4 mA
Seven-segment LED
No
60 to 80 m
Coverage
Polarity sensitive
Yes
DP2071
DP2061
DT2073
DT2063
17 to 28 VDC
17 to 28 VDC
< 150 µA
< 150 µA
4 mA
2 mA
4 mA
4 mA
Yes
No
2
2
60 to 80 m
60 to 80 m
No
No
P/N 55370158 • REV 8.0 • ISS 05OCT11
2