Universal Input KNX-S
6

Commissioning

Programming the physical address and application program
Switch on the bus voltage.
Press the programming button (2).
The programming LED (3) lights up.
Program the physical address with the ETS.
The programming LED goes out.
Program the application program with the ETS.
6.1

Safe-state mode and master reset

Safe-state mode
The safe-state mode stops the execution of the loaded application program.
Only the system software of the device is still functional. ETS diagnosis func-
tions and programming of the device are possible.
Activating safe-state mode
Switch off the bus voltage or remove the KNX device connection terminal.
Wait approx. 10 seconds.
Press and hold down the programming button.
Switch on the bus voltage or attach the KNX device connection terminal.
Wait until the programming LED flashes slowly.
Release the programming button.
The safe-state mode is activated.