The transmitter can be adjusted and/or calibrated with the help of a
Windows 95/98 calibration program in combination with an applicable
interface that can be plugged into any RS232 serial PC-port. The
calibration data is stored in the non-volatile memory in the transmitter. After
calibration the transmitter functions as a stand alone device
(consult factory for more details).
PC interface is needed to calibrate the transmitter. With this interface the
transmitter can be connected to the serial RS232 port of a computer. At
power/start-up the transmitter is waiting (~2 seconds) for serial
communication before entering normal operation. When a serial
communication is established, the transmitter is instructed to sustain its
low-power mode (typically 2.6 mA). In this low-power mode the transmitter
is directly powered from the RS232 port without the need of an external
power supply.
Software Kit (Calibration CD-ROM and RS232 Interface): partnumber:
F535Y001ZZZ
Installation and Operation Manual
X-VA-MT3750C-eng
Part Number: 541B063AAG
October, 2017