A03
Auto-sync current (will only show when A01 is set to LEGACY). When the charge current is
below this percentage of the battery capacity (see Function F1.1), the battery will be
considered as fully charged. Make sure that this value is always slightly greater than the
current at which the charger maintains the battery or stops charging.
Default: 2.0%
A04
Auto-sync time (will only show when A01 is set to LEGACY). This is the time that both
Auto-sync parameters A02 and A03 must be met in order to consider the battery as fully
charged.
Default: 240sec
A05
Auto-sync sensitivity (will only show when A01 is set to LEGACY). Only change this setting
when A02, A03 and A04 are set correctly and automatic synchronization still fails. If
automatic synchronization takes too long or does never occur, lower this value. When the
battery monitor synchronizes too early, increase this value.
Default: 5
A07
Bank 1 series cell count. Allows you to edit the number of internal series cells of your used
batteries that was automatically determined after completing the Setup Wizard. See table
2 in chapter 2.2 for more information.
Default: dynamic
A08
Bank 2 series cell count (will only show when F2.0 is set to AUX.BAT). Allows you to edit
the number of internal cells of your used batteries, that was automatically determined
after completing the Setup Wizard. See table 2 in chapter 2.2 for more information.
Default: dynamic
A09
Bank 3 series cell count (will only show when F3.0 is set to AUX.BAT). Allows you to edit
the number of internal cells of your used batteries, that was automatically determined
after completing the Setup Wizard. See table 2 in chapter 2.2 for more information.
Default: dynamic
A10
Force SoC on Start-up. Allows you to choose at what SoC (%) level the Expert Modular
should start-up after a supply voltage interruption. All available options are described in
table 11.
Default: OFF
Table 11
Value
Description
OFF
Automatic SoC prediction for lead based batteries and no SoC value for lithium
batteries (lithium requires full charge cycle to obtain SoC value)
NO.SOC
No SoC value (display shows '- -'). Requires a full charge cycle for all battery types
to obtain SoC value
LAST.SOC
The last stored SoC value just prior to a supply voltage interruption will be shown
after start-up.
0% - 100%
Display shows 0% to 100% SoC after restart (step size is 10%)
Range: 0.5 - 10.0%
Range: 0 – 3600sec
Range: 0 – 10
Range: 2 – 30
Range: 2 – 30
Range: 2 – 30
Range: see table 11
25
Step size: 0.1%
Step size: variable
Step size: 1
Step size: 1
Step size: 1
Step size: 1