7. TROUBLESHOOTING
Problem
No display appears
Display shows
when button / setting
dial is activated
Manual watering is
not possible using the
button
Watering program is
not being undertaken
(no watering)
1890-20.960.06.indb 17
1890-20.960.06.indb 17
Possible Cause
Battery is inserted incorrectly.
Battery is flat.
Temperature on the display is higher
than 70 °C.
Buttons have been locked.
Low battery is continuously displayed.
Tap is turned off.
Controller is not connected.
Minimum pressure of 0.5 bar not
available.
Program entry / modification during or
just before the start pulse.
Valve was opened manually previously.
Tap is turned off.
Soil moisture or rain sensor registers damp.
Controller is not connected.
Remedy
v Check the polarity markings
match (+ / –).
v Insert a new (alkaline) battery.
v Display appears after the
temperature has dropped.
v Press the
button for 3 seconds.
v Insert a new (alkaline) battery.
v Turn the tap on.
v Mount the controller on housing.
v Ensure a pressure of at least
0.5 bar.
v Make program entry / modification
outside the programmed start times.
v Avoid possible program overlaps.
v Turn the tap on.
v If dry, check the setting / location of
the soil moisture / rain sensor.
v Mount the controller on housing.
17