SWIMMING POOL HEAT PUMP TYPE PX
4.6 Temperature curve
In the main interface, click the curve display button, interface displays
as follows:
4.6.1 The temperature curve
4.6.2 The average power input curve
Temperature curve automatically updates every one hour, and the curve
can be stored for 60 days;
Start from the latest curve saved time, if power is off and curve data
collecting time is less than one hour, the data in this period will not be
saved.
WWW.NORSUP.EU
26
Alterations which serve the technological progress as well as errors excepted!
SWIMMING POOL HEAT PUMP TYPE PX
4.7. Electronic control fault table
Can be judged according to the remote controller failure code
and troubleshooting
Protect/fault
Fault
Reason
display
The temp. sensor is broken or short
Inlet Temp. Sensor Fault
P01
circuit
The temp. sensor is broken or short
Outlet Temp. Sensor Fault
P02
circuit
The temp. sensor is broken or short
Ambient Temp. Sensor Fault
P04
circuit
The temp. sensor is broken or short
Coil 1 Temp. Sensor Fault
P05
circuit
The temp. sensor is broken or short
Coil 2 Temp. Sensor Fault
P15
circuit
The temp. sensor is broken or short
Suction Temp. Sensor Fault
P07
circuit
The temp. sensor is broken or short
Discharge Temp. Sensor Fault P081
circuit
Exhaust Air Over-Temp Prot. P082
The compressor is overload
The temp. sensor is broken or short
Antifreeze Temp. Sensor Fault
P09
circuit
Pressure Sensor Fault
PP
The pressure sensor is broken
High Pressure Prot.
E01
The high-pressure switch is broken Check the pressure switch and cold circuit
Low Pressure Prot.
E02
The low-pressure switch is broken
The temp. sensor is broken or short
Flow Switch Prot.
E03
circuit
No water/little water in water
Waterway Anti-freezing Prot.
E05
system
Water flow is not enough and low
Inlet and outlet temp. too
E06
differential pressure
big
Anti-freezing Prot.
Water flow is not enough
E07
Primary Anti-freezing Prot.
The ambient temp. is low
E19
Secondary Anti-freezing Prot. E29
The ambient temp. is low
Comp. Overcurrent Prot.
E051 The compressor is overload
Communication failure between
Communication Fault
E08
wire controller and mainboard
Communication Fault
E081 Speed control module and main
board communication fail
(speed control module)
The ambient temp. is low
Low AT Protection
TP
There is something wrong with
EC fan feedback Fault
F051
fan
motor and fan motor stops
1. Motor is in locked-rotor state
running
2.The wire connection between
Fan Motor1 Fault
F031
DC-fan motor module and fan
motor is in bad contact
Alterations which serve the technological progress as well as errors excepted!
DE
EN
Elimination
EN
NL
methods
Check or change the temp. sensor
Check or change the temp. sensor
DE
Check or change the temp. sensor
Check or change the temp. sensor
Check or change the temp. sensor
FR
Check or change the temp. sensor
Check or change the temp. sensor
Check whether the compressor
running normally
Check or change the temp. sensor
DA
Check or change the pressure sensor
or pressure
Check the pressure switch and cold circuit
SV
Check or change the temp. sensor
Check the pipe water flow and water
pump
Check the pipe water flow and whether
water system is jammed or not
Check the pipe water flow and whether water
system is jammed or not
Check whether the ambient temp. is low or
not
Check whether the ambient temp. is low or
not
Check whether the system of the
compressor running normally
Check the wire connection between
remote wire controller and main board
Check the communication connection
Check whether the ambient temp. is low or
not
Check whether fan motor is broken or locked or
not
1.Change a new fan motor
2.Check the wire connection and make
sure they are in good contact