5. Technical data
Phoenix Inverter
Cont. power at 25°C
Cont. power at 25°C / 40°C
Peak power
Output AC voltage / frequency (adjustable)
Input voltage range
Low battery shut down (adjustable)
Low battery restart & alarm (adjustable)
Battery charged detect (adjustable)
Max. efficiency
Zero-load power
Default zero-load power in ECO mode
(default search interval: 2,5 s, adjustable)
ECO mode stop and start power setting
Protection
(2)
Operating temperature range
Humidity (non-condensing)
Material & Colour
Battery-connection
Maximum cable cross-section
Standard AC outlets
Protection category
Weight
Dimensions (hxwxd, mm)
(hxwxd, inch)
Remote on-off
Automatic transfer switch
Safety
EMC
Automotive Directive
1) Nonlinear load, crest factor 3:1
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) DC ripple too high
6
12 Volt
24 Volt
48 Volt
(1)
ENCLOSURE
ACCESSORIES
STANDARDS
12/250
24/250
48/250
250 VA
200 / 150 W
350 W
230 VAC +/- 3% 50Hz or 60Hz +/- 0,1%
9,2 - 17 / 18,4 - 34,0 / 36,8 - 62,0 VDC
9,3 / 18,6 / 37,2 VDC
10,9 / 21,8 / 43,6 VDC
14,0 / 28,0 / 56,0 VDC
87 / 88 / 88%
4,2 / 5,2 / 7,9 W
0,8 / 1,3 / 2,5 W
25 W
a - f
-40 to +60°C (fan assisted cooling)
(derate 3% per °C above 40°C)
max 95%
Steel chassis and plastic cover (blue Ral 5012)
Screw terminals
10 mm² / AWG8
Schuko (CEE 7/4), IEC-320 (male plug included)
UK (BS 1363), AU/NZ (AS/NZS 3112)
IP 21
2,4 kg / 5,3 lbs
86 x 165 x 260
3,4 x 6,5 x 10,2
Yes
Filax
EN/IEC 60335-1 / EN/IEC 62109-1
EN 55014-1 / EN 55014-2
IEC 61000-6-1 / IEC 61000-6-3
2004/104/EC
12/375
24/375
48/375
375 VA
300 / 250 W
700 W
89 / 89 / 90%
5,6 / 6,1 / 8,5 W
0,9 / 1,4 / 2,6 W
10 mm² / AWG8
3,0 kg / 6,6 lbs
86 x 165 x 260
3,4 x 6,5 x 10,2
EN 50498